ROME, NY —
OSHA Inspection: GOODRICH CORPORATION
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of GOODRICH CORPORATION in 104 OTIS STREET, ROME, NY 13441 (NAICS 336413). OSHA activity number 340812429.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GOODRICH CORPORATION
- Site address
- 104 OTIS STREET
- City
- ROME
- State
- NY
- ZIP
- 13441
- Mailing
- 104 OTIS STREET, ROME, NY 13441
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336413
- Employees
- 220
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.23 A08
- Issued
- Nov 10, 2015
- Penalty
- Initial $3,400 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.23(a)(8): Floor hole(s), into which persons could accidentally walk, were not guarded by standard railings with standard toeboards on all exposed sides or by floor hole covers of standard strength and construction: a) ECM Filter Press Room, on or about 7/31/15: A floor hole approximately 12.5nches by 9.5 inches was not guarded.
Recent events (2)
- — I (S) $1575
- — Z (S) $3400
1910.106 D03 II A
- Issued
- Nov 10, 2015
- Abate by
- Nov 26, 2015
- Penalty
- Initial $3,400 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.106(d)(3): 29 CFR 1910.106(d)(3)(ii)(a): Metal cabinets constructed in the following manner shall be deemed to be in compliance. The door shall be provided with a three point lock. a) Aircraft Shafts Paint Booth Area, on or about 7/31/15: A flammable storage cabinet containing 55 gallon waste drum had a broken three point lock on the door. b) Industrial Couplings EBW Area, on or about 7/31/15: A flammable storage cabinet containing containers of Magna Flux had a broken three point lock on the door.
Recent events (2)
- — I (S) $2100
- — Z (S) $3400
1910.106 E06 II
- Issued
- Nov 10, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(e)(6)(ii): Class I flammable liquid(s) were dispensed into containers without electrically interconnecting the nozzle and the container: a) Industrial Couplings Paint Booth Area, on or about 7/31/15: Employees dispense flammable waste from one container to a 30 gallon secondary container of flammable waste with no means of electrically interconnecting the nozzle and the pump.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.215 B09
- Issued
- Nov 10, 2015
- Penalty
- Initial $2,168 · Current $1,339 Reduced
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: a) Air Craft Shafts Machining Cell, on or about 7/31/15: A Blaldor Bench Grinder had an opening between the tongue guard and grinding wheel that measured 1/2-inch at both wheels.
Recent events (2)
- — I (S) $1338.75
- — Z (S) $2168
1910.242 B
- Issued
- Nov 10, 2015
- Penalty
- Initial $3,400 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: a) Aircraft Shafts Paint Booth Area, on or about 7/31/15: Employees using compressed air for cleaning purposes was measured at approximately 100 p.s.i. a) Industrial Coupling VMC 900 C Area, on or about 7/31/15: Employees used compressed air for cleaning purposes was measured at approximately 80 p.s.i. b) Aircraft Shafts Tube Cell Area, on or about 7/31/15: Employees used compressed air for cleaning purposes was measured at approximately 85 p.s.i. c) F20 - Aircraft Shafts Paint Booth Area, on or about 7/31/15: Employees used compressed air for cleaning purposes was measured at approximately 100 p.s.i.
Recent events (2)
- — I (S) $2100
- — Z (S) $3400
1910.303 B02
- Issued
- Nov 10, 2015
- Penalty
- Initial $2,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Air Craft Shafts Machining Cell Area, on or about 7/31/15: At Column C7 a Tripp Lite Power Strip was being used to plug in two Baldor Bench Grinders. The extension cord is being used against UL approval.
Recent events (2)
- — I (O) $0
- — Z (S) $2550
1910.146 C07 III
- Issued
- Nov 10, 2015
- Abate by
- Dec 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.146(c)(7)(iii): The employer did not document the basis for determining that all hazards in a permit space had been eliminated, through a written certification that contained the date, the location of the space, and the signature of the person making the determination: a) Throughout the Facility, on or about 8/4/15: The permit required confined space program did not have a written certification when the permit required confined spaces were declassified to non permit confined spaces.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Goodrich Corporation
View Goodrich Corporation's full OSHA safety record →
More inspections in this industry (NAICS 336413)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340812429.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.