BROWNSVILLE, TX —
OSHA Inspection: RICH PRODUCTS CORPORATION
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of RICH PRODUCTS CORPORATION in 3555 EAST 14TH, BROWNSVILLE, TX 78521 (NAICS 424420). OSHA activity number 340815331.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RICH PRODUCTS CORPORATION
- Site address
- 3555 EAST 14TH
- City
- BROWNSVILLE
- State
- TX
- ZIP
- 78521
- Mailing
- 3555 EAST 14TH, BROWNSVILLE, TX 78521
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424420
- Employees
- 260
- Ownership type
- A
Citations
15 citations on file for this inspection.
1910.95 G08 I
- Issued
- Jan 21, 2016
- Penalty
- Initial $6,600 · Current $6,600
General-duty citation text
29 CFR 1910.95(g)(8)(i): When a comparison of the annual audiogram to the baseline audiogram indicates a standard threshold shift, as defined in 29 CFR 1910.95(g)(10) has occurred, the employee was not informed of this fact in writing, within 21 days of the determination: The employer did not provide employees in writing of a threshold shift employees whose noise exposure levels exceeded the action level 85dbA, the employer was notified of employees threshold shifts on December 11, 2014 as follows: Employee S6 was determined to have a threshold shift on December 11, 2014 Employee S5 was determined to have a threshold shift on December 11, 2014
Recent events (2)
- — I (S) $6600
- — Z (S) $6600
1910.95 G08 II B
- Issued
- Jan 21, 2016
- Penalty
- Initial $6,600 · Current $6,600
General-duty citation text
29 CFR 1910.95(g)(8)(ii)(B): Unless a physician determines that the standard threshold shift is not work-related or aggravated by occupational noise exposure, the employer did not ensure, when a standard threshold shift occurs, that for employees already using hearing protectors, employees be refitted and retrained in the use of hearing protectors and provided with hearing protectors offering greater attenuation if necessary: Employees exposed to noise exposure levels which exceeded the action level of 85 dbA were not refitted with hearing protection with greater attenuation or retrained on the use of hearing protectors after employer was notified of their possible standard threshold shift.
Recent events (2)
- — I (S) $6600
- — Z (S) $6600
1910.95 G08 II C
- Issued
- Jan 21, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.95(g)(8)(ii)(C): Unless a physician determines that the standard threshold shift is not work-related or aggravated by occupational noise exposure, the employer did not ensure, when a standard threshold shift occurs, the employee was referred for a clinical audiological evaluation or an ontological examination, as appropriate, if additional testing is necessary or if the employer suspects that a medical pathology of the ear is caused or aggravated by wearing of hearing protectors: The employer did not ensure a physician determined that the standard threshold shift was not work-related.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.119 D03 II
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: This violation was most recently observed on or about July 23, 2015 and times thereafter, in the Ammonia Refrigeration Process at Rich Products Corporation located in Brownsville, Texas when the engine room front and back access doors were not equipped with tight-fitting seal and self-closing as stipulated in RAGAGEP (Recognized and Generally Accepted Engineering Practice) such as but not limited to ANSI/ASHRAE Standard 15 - 2013 section 8.12.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.119 E05
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.119(e)(5): The employer did not establish a system to promptly address the team's findings and recommendations: This violation was most recently observed on or about July 23, 2015 and times thereafter, in the Ammonia Refrigeration Process at Rich Products Corporation located in Brownsville, Texas; when the employer did not resolve in a timely manner the 2014 PHA team's findings and recommendations; including but not limited to: 1. Site associates must ensure Piping and Instrument Diagram (P&ID) are updated appropriately following MOC changes (BRO-PHA-1404). Target Date of Completion 11/2014. As of July 23, 2015 this PHA item had not been completed. 2. Site associates should evaluate the practice of having the delivery truck pull a vacuum prior to disconnection as an SOP (BRO-PHA-1417). Target Date of Completion 01/2015. As of July 23, 2015 this PHA item had not been completed. 3. Should the response activities be outsourced, site associates should document their Memorandum of Understanding (MOU) with the local fire department and the Local Emergency Planning Commission (LEPC) (BRO-PHA-1421). Target Date of Completion 04/2015. As of July 23, 2015 this PHA item had not been completed.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.119 J02
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not implement written procedures to maintain the on-going integrity of process equipment. This violation was most recently observed on or about July 23, 2015 in the engine room when the employer did not implement Mechanical Integrity procedure to ensure the insulation on process piping such as but not limited to -49 F Recirculator Outlet to Main Liquid Valve was repaired and sealed to prevent condensation and corrosion.
Recent events (2)
- — I (O) $3500
- — Z (S) $7000
1910.119 J05
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation. This violation was most recently observed on or about July 23, 2015 in the engine room when the employer failed to ensure the insulation on process piping such as but not limited to -49 F Recirculator Outlet to main liquid valve was repaired and sealed to prevent condensation and corrosion.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.119 J04 I
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment: This violation was most recently observed on or about July 23, 2015 and times thereafter, in the Ammonia Refrigeration Process at Rich Products Corporation located in Brownsville, Texas when the employer failed to perform inspections and tests on the eight Ammonia detectors (Honeywell Analytics) and alarms located in the machine room, freezers, cooler and dock area.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.119 L04
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $3,300 · Current $3,300
General-duty citation text
29 CFR 1910.119(l)(4): When a change covered by this paragraph resulted in a change in the process safety information required by paragraph (d) of this section, such information was not updated accordingly. This violation was most recently observed on or about July 23, 2015 and times thereafter, in the Ammonia Refrigeration Process at Rich Products Corporation located in Brownsville, Texas when the Piping and Instrument Diagram (P&ID) was not updated to reflect the addition of the 6-inch relief header in 2012.
Recent events (2)
- — I (S) $3300
- — Z (S) $3300
1910.120 Q01
- Issued
- Jan 21, 2016
- Abate by
- Feb 12, 2016
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.120(q)(1): The employer did not develop and implement an emergency response plan to handle anticipated emergencies prior to commencement of emergency response operations: On or about July 23, 2015 and times thereafter, the employer did not implement an emergency response plan that addressed provisions, such as but not limited to pre-emergency planning and coordination with outside parties such as with the Brownsville Fire Departments.
Recent events (2)
- — I (O) $3500
- — Z (S) $7000
1910.134 E01
- Issued
- Jan 21, 2016
- Abate by
- Feb 12, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: On or about July 23, 2015, in the Ammonia Refrigeration Process at Rich Products, LLC located in Brownsville, Texas, the employer did not ensure employees who are required to use tight-fitting facepiece respirators were provided with a medical evaluation prior to use.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.134 F02
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.134(f)(2): The employer did not ensure that an employee using a tight-fitting facepiece respirator was fit tested prior to initial use of the respirator, and at least annually thereafter. On or about July 23, 2015, in the Ammonia Refrigeration Process at Rich Products, LLC located in Brownsville, Texas, the employer did not ensure employees who are required to use tight-fitting facepiece respirators were fit tested at least annually.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.119 F01 I B
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $27,500 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.119(f)(1)(i)(B): The employer's written operating procedures covering the steps for each operating phase did not address normal operations; Throughout the ammonia refrigeration system, on or about July 23, 2015 and at times prior to, the standard operating procedures were not adequate, in that a single oil pot draining procedure was developed for vessels that were maintained at positive pressure (-28 F Recirculator and +15 F Intercooler) and negative pressure (-49 F Recirculator). Rich Products Corporation was previously cited for a violation of this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.119(f)(1)(i)(B): which is contained in OSHA Inspection Number 314096546, Citation Number 1 Item 9 a, issued on May 16, 2012 with respect to a workplace located at 200 Glyndale Drive, Brunswick, GA. This file became Final Order on June 7, 2012.
Recent events (2)
- — I (S) $7000
- — Z (R) $27500
1910.119 D03 I D
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $27,500 · Current $27,500
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Process safety information pertaining to the equipment in the process did not include Relief system design and design basis; This violation was most recently observed on or about July 23, 2015 and times thereafter, in the Ammonia Refrigeration Process at Rich Products Corporation located in Brownsville, Texas when the process safety information did not include the relief system design and design basis. Rich Products Corporation was previously cited for a violation of this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.119(d)(3)(I)(D): which is contained in OSHA Inspection Number 314096546, Citation Number 1 Item 8 a, issued on May 16, 2012 with respect to a workplace located at 200 Glyndale Drive, Brunswick, GA. This file became Final Order on June 7, 2012.
Recent events (2)
- — I (R) $27500
- — Z (R) $27500
1910.119 D03 I E
- Issued
- Jan 21, 2016
- Abate by
- Mar 7, 2016
- Penalty
- Initial $27,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(E): Process safety information pertaining to the equipment in the process did not include the ventilation system design; This violation was most recently observed on or prior to July 23, 2015 in the Ammonia Refrigeration Process at Rich Products Corporation located in Brownsville, Texas when accurate calculations of the engine room ventilation system design and design basis were not included in the process safety information. Rich Products Corporation was previously cited for a violation of this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.119(d)(3)(i)(E): which is contained in OSHA Inspection Number 314096546, Citation Number 1 Item 6 b, issued on May 16, 2012 with respect to a workplace located at 200 Glyndale Drive, Brunswick, GA. This file became Final Order on June 7, 2012.
Recent events (2)
- — I (R) $0
- — Z (R) $27500
More inspections at Rich Products Corporation
View Rich Products Corporation's full OSHA safety record →
More inspections in this industry (NAICS 424420)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340815331.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.