ST THOMAS, VI —
OSHA Inspection: INNOVATIVE COMMUNICATIONS-BASFORD
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of INNOVATIVE COMMUNICATIONS-BASFORD in BASFORD TELEPHONE BUILDING, ST THOMAS, VI 00805 (NAICS 517110). OSHA activity number 340817311.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INNOVATIVE COMMUNICATIONS-BASFORD
- Site address
- BASFORD TELEPHONE BUILDING
- City
- ST THOMAS
- State
- VI
- ZIP
- 00805
- Mailing
- P.O. BOX 6100, ST THOMAS, VI 00801
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 517110
- Employees
- 46
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 G01 I
- Issued
- Jan 15, 2016
- Penalty
- Initial $3,825 · Current $3,825
General-duty citation text
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: Instance #1: On or about 07/21/2015, Innovative Communications-Basford bldg., St. Thomas VI- I.T. hallway electrical Panels area: Access to electrical panels was blocked with supplies and cardboard boxes. Instance #2: On or about 07/21/2015, Innovative Communications-Basford bldg., St. Thomas VI- Installers permanent dispatch-electrical Panels area: Access to electrical panels was blocked with cardboard boxes. Note for instances #1 & #2: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (1)
- — Z (S) $3825
1910.303 G02 I
- Issued
- Jan 15, 2016
- Abate by
- Feb 11, 2016
- Penalty
- Initial $3,825 · Current $3,825
General-duty citation text
29 CFR 1910.303(g)(2)(i):Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: a: On or about 07/21/2015, Innovative Communications-Basford bldg., St. Thomas VI- I.T. hallway electrical Panels area: Employees were using an electrical panel that have missing breakers exposing live bus bars, therefore, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact. Note: Certification of abatement must submitted for these citation items as required by 29 CFR 1903.19(c).
Recent events (1)
- — Z (S) $3825
More inspections at Innovative Communications-Basford
View Innovative Communications-Basford's full OSHA safety record →
More inspections in this industry (NAICS 517110)
More inspections in VI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340817311.