Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NOAA NORTHWEST FISHERIES SCIENCE CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NOAA NORTHWEST FISHERIES SCIENCE CENTER in 2725 MONTLAKE BLVD EAST, SEATTLE, WA 98112 (NAICS 541712). OSHA activity number 340826452.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Noaa Northwest Fisheries Science Center — free Get an email when a new federal OSHA severe-injury report for Noaa Northwest Fisheries Science Center is published. One employer, no account, unsubscribe in one click.
Site address
2725 MONTLAKE BLVD EAST
City
SEATTLE
State
WA
ZIP
98112
Mailing
2725 MONTLAKE BLVD EAST, SEATTLE, WA 98112
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541712
Employees
207
Ownership type
D

13 citations on file for this inspection.

1910.23 E01

Serious Gravity 5 2 instances 6 exposed
Issued
Sep 23, 2015
Abate by
Aug 31, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.23(e)(1): Standard railing(s) did not consist of top rail, intermediate rail and/or posts and/or did not have a vertical height of 42 inches (106.7 cm) nominal from upper surface of top rail to floor, platform runway, or ramp level:  a)  Auditorium Mezzanine;  The railing measured 36 inches high with a 15 foot 4 inch fall to the lower level.   b)  Four breezeways had railings which measured 37 inches high exposing employees to more than a 15 foot fall.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:   a)  Welding Area;  The Niagard Shear did not have guarding to prevent employees from accessing the rear of the machine where the cut material falls to the floor.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 11 instances 11 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)  Aqua Lab West;  A relocatable power tap powered a water/air pump adjacent to pools of water.   b)  Auditorium;  Metal handy boxes made into heavy duty extension cords were not mounted and the box was moveable.   c)  Library;  An electric kettle was plugged into an  extension cord.   d)  Maintenance Managers Office;  A relocatable power tap was plugged into another relocatable power tap.   e)  Locker Area, Maintenance Shop;  A Keurig coffee/tea maker, DeLonghi toaster over and Kenmore microwave oven were plugged into a relocatable power tap which was plugged into an extension cord (daisy chain).   f)  Room 332 East;  A Sharp microwave and brown mini-refrigerator were plugged into a relocatable power tap.   g)  Conference Room 438 East;  A relocatable power tap was plugged into a handy box extension cord (daisy chain), which powered a polycom phone, TV and other audio visual equipment.    h)  Conference Room 438 East;  A handy box extension cord was plugged into an extension cord (daisy chain).   i)  Room 402 East;  A portable heater was plugged into a relocatable power tap. Room 102 South;  An electric kettle was plugged into a relocatable power tap.   j)  Room 216 South;  A Therapure dehumidifier was plugged into a relocatable power tap.   The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.      The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances.  This exposes employees to possible electrical fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 1 2 instances 4 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a)       FRAM lab, Pilot Plant;  Five florescent lights were unguarded and adjacent to stored equipment on shelves.   b)      Kitchen Room 432 East;  Unguarded florescent lights were located approximately1-2 feet from the counter top.
Recent events (1)
  • — Z (S) $0

1910.305 B01 I

Serious Gravity 1 3 instances 6 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:  a)  Room 371 West;  A knockout was missing on the breaker panel for the lights.   b)  Panel 3C West Building, A knockout was missing on the outlet box.   c)  Panel 1A West; Knockouts were missing on the outlet boxes for the drinking fountain.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a)       Chlorine Shed;  The LB box was not covered and it powered outlets.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 2 instances 2 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a)      Auditorium;  A water cooler was plugged into an extension cord.   b)      East Building North Conference Room;  A phone was plugged into an extension cord for longer than 90 days.
Recent events (1)
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 1 4 instances 6 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service:  a)  Pilot Plant Engineering Lab;  A Rockwell 7 ½ inch builders saw had duct tape on its strain relief.   b)  Pilot Plant Engineering Lab;  A large solder iron had several areas of damage to its power cord.   c)  Welding Area;  A Black and Decker saw had damaged outer sheathing/ strain relief.  d)  Room 456 East; A Kinematica blenders power cord was pulled from its strain relief, exposing insulated wires.
Recent events (1)
  • — Z (S) $0

1910.36 G02

Other-than-serious 4 instances 8 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a)  Library- A bookshelf filled with books had a 16 inch aisleway.  b)  2nd Floor Walk in Freezer adjacent to Room 245 East;  The walk in freezer was overly full with boxes and other stored items which were interfering with the clear aisleway to the rear of the freezer.  c)  Room 305 East;  There was a 16 inch aisleway between an orange chair and a desk.   d)  Room 102 South;  There was a 25 inch aisleway between a desk and some file cabinets.
Recent events (1)
  • — Z (O) $0

1910.37 B02

Other-than-serious 1 instance 5 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   a)  The exit discharge door in the Hatchery did not have an exit sign.
Recent events (1)
  • — Z (O) $0

1910.37 B04

Other-than-serious 3 instances 5 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  a)  A directional exit sign was needed in the hatchery north laboratory.   b)  A directional exit sign was needed on the outer wall of the isolation laboratory.   c)  A directional exit sign was needed in the downstairs hatchery pool area.
Recent events (1)
  • — Z (O) $0

1910.37 B05

Other-than-serious 2 instances 5 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  a)  A door in the downstairs hatchery pool area lead to a dead end and did not have a NOT AN EXIT sign.   b)  The door leading to the downstairs hatchery pool area lead to a dead end and  was not labeled NOT AN EXIT.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 2 instances 6 exposed
Issued
Sep 23, 2015
Abate by
Oct 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a)      Dive Locker;  Diving equipment (dive bags, weighted belts) were stored underneath the breaker panel.   b)      Maintenance Shop Tool Room;  A shop vacuum and other items were stored underneath the breaker panel.
Recent events (1)
  • — Z (O) $0

View Noaa Northwest Fisheries Science Center's full OSHA safety record →