EL CENTRO, CA —
OSHA Inspection: NAVAL AIR FACILITY EL CENTRO
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NAVAL AIR FACILITY EL CENTRO in AUTO HOBBY SHOP BLDG. 362, EL CENTRO, CA 92243 (NAICS 811198). OSHA activity number 340833383.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAVAL AIR FACILITY EL CENTRO
- Site address
- AUTO HOBBY SHOP BLDG. 362
- City
- EL CENTRO
- State
- CA
- ZIP
- 92243
- Mailing
- NAVAL AIR FACILITY EL CENTRO 1605 THIRD STREET, BLDG. 214, EL CENTRO, CA 92243
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811198
- Employees
- 2
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.157 E02
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: Garage: Two fire extinguishers were last visually inspected June 2014.
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: Garage: Two fire extinguishers present in the garage since April 2013 have not had annual maintenance checks.
Recent events (1)
- — Z (S) $0
1910.212 A01
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: Garage: Employees were exposed to injury by the unguarded rotating parts of a West Brake lathe, Model Number 1115HD, serial number A011V1013 used to service automotive brake parts.
Recent events (1)
- — Z (S) $0
1910.212 A05
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level: Garage: Employees were exposed to injury by the unguarded fan blades of a 48 inch Polar Cool portable evaporative cooling system pulley where the employees used the system without the paper media pads installed to prevent inadvertent contact with the fan blades. MWR property # 000235, Navy property number N60042-12602
Recent events (1)
- — Z (S) $0
1910.219 D01
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): Garage: Employees were exposed to injury by the unguarded rotating parts and nip points of a 48 inch Polar Cool portable evaporative cooling system pulley where the employees used the system without the paper media pads installed to prevent inadvertent contact with the pulley. MWR property # 000235, Navy property number N60042-12602
Recent events (1)
- — Z (S) $0
1910.219 E03 I
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o): Garage: Employees were exposed to injury by the unguarded rotating parts and nip points of a 48 inch Polar Cool portable evaporative cooling system belt where the employees used the system without the paper media pads installed to prevent inadvertent contact with the belt. MWR property # 000235, Navy property number N60042-12602
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Sep 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Office: A power strip was used to provide 120VAC electrical service to a small white refrigerator and a GE Profile microwave.
Recent events (1)
- — Z (S) $0
1910.303 B07 IV
- Issued
- Sep 24, 2015
- Abate by
- Oct 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating: Garage: Employees were exposed to inadvertent contact with live 120VAC conductors where a receptacle cover plate had a corner broken off exposing the conductors inside the box.
Recent events (1)
- — Z (S) $0
More inspections at Naval AIR Facility EL Centro
View Naval AIR Facility EL Centro's full OSHA safety record →
More inspections in this industry (NAICS 811198)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340833383.