OSHA Inspection: NAVAL AIR FACILITY EL CENTRO

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVAL AIR FACILITY EL CENTRO in NAVAL AIR FACILITY EL CENTRO BLDG. 214, EL CENTRO, CA 92243 (NAICS 928110). OSHA activity number 347787053.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Naval AIR Facility EL Centro — free Get an email when a new federal OSHA severe-injury report for Naval AIR Facility EL Centro is published. One employer, no account, unsubscribe in one click.
Site address
NAVAL AIR FACILITY EL CENTRO BLDG. 214
City
EL CENTRO
State
CA
ZIP
92243
Mailing
NAVAL AIR FACILITY EL CENTRO 1605 THIRD STREET, BLDG. 214, EL CENTRO, CA 92243
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
10
Ownership type
D

7 citations on file for this inspection.

1910.37 A04

Serious Gravity 1 1 instance 10 exposed
Issued
Oct 24, 2024
Abate by
Oct 30, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.  VTC room, Bldg. 214: On or about October 1st, 2024 at times prior thereto, a ceiling panel in the VTC room was improperly installed. This condition would delay the activation of the sprinkler system(s) preventing a proper fire/smoke barrier and restricting the movement of smoke in accordance with NFPA 101 8.5.1. This condition potentially exposed employee(s) to fire and smoke inhalation hazard(s).
Recent events (1)
  • — Z (S) $0

1910.38 C02

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 24, 2024
Abate by
Nov 5, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.38(c)(2): Procedures for emergency evacuation, including type of evacuation and exit route assignments were not implemented by the employer.   Restricted room, Main Bldg: On or about October 1st, 2024, and at times prior thereto, employee(s) engaged in security and technical operation(s). The employer's EAP plan did not include a review to show employee(s) where and/or how to evacuate in the event of an emergency specifically for, controlled access space(s). Employee(s) were potentially exposed to fire hazard(s) and/or egress hazard(s).
Recent events (1)
  • — Z (S) $0

1910.38 C04

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 24, 2024
Abate by
Nov 5, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.38(c)(4): The emergency action plan does not include procedures to account for all employees after evacuation.  Restricted room, Main Bldg: On or before October 1st, 2024, and at times prior thereto employee(s) engaged in security and technical operation(s). The employer did not include accountability procedures in the Emergency Action Plan to show employee(s) where to evacuate in the event of an emergency specifically for, controlled space(s). This condition potentially exposed employee(s) to fire hazard(s) and/or egress hazard(s).
Recent events (1)
  • — Z (S) $0

1910.157 E02

Serious Gravity 5 5 instances 10 exposed
Issued
Oct 24, 2024
Abate by
Nov 5, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly.  On or about October 1st, 2024, and at times prior thereto, fire extinguisher(s) had not been subject to their monthly maintenance check(s). This condition potentially exposed employee(s) to extinguisher mechanical failure to put out and/or escape incipient fire hazard(s).  In the following location(s):  a) Safety Office, Room 127, Bldg. 214 b) IT/ emergency management office, Room 124 c) ID cards and Deers office, Room 112 d) Main Building  e) All fire extinguishers within the interior and exterior of bldg.214.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 24, 2024
Abate by
Oct 30, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling.  IT Emergency Management Office, Room 125, Bldg. 214: On or ABOUT October 1st, 2024, and at times prior thereto a Levoit True HEPA Air Purifier was plugged into a relocatable power tap in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 24, 2024
Abate by
Oct 31, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  Safety Office, Room 127, Bldg. 214: On or about October 1st, 2024, and at times prior thereto the employer did not ensure at least 3 feet in front of the electrical panel was clear. The circuit breaker panel had two (2) storage racks, two (2) vacuum cleaner(s), multiple boxes and computer monitor(s) obstructing the panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 5 2 instances 3 exposed
Issued
Oct 24, 2024
Abate by
Oct 31, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  On or about October 1st, 2024, and at times prior thereto employee(s) used the TASKVAC commercial vacuum cleaner to vacuum the office spaces. Also, employee(s) used the Belkin 7-Outlet SurgeMaster Surge Protector to plug a Levoit True HEPA Air Purifier and a WOOZOO Fan Circulator. The TASKVAC commercial vacuum cleaner and the Belkin 7-Outlet SurgeMaster Surge Protector  was not visually inspected for exposed wiring. This condition potentially exposed employee(s) to electrical shock and/or fire hazards.  In the following location(s): a) Safety Office, Room 127, Bldg. 214 - TASKVAC commercial vacuum cleaner. b) IT Emergency Management Office, Room 125, Bldg. 214 - Belkin 7-Outlet SurgeMaster Surge Protector.
Recent events (1)
  • — Z (S) $0