Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: W W WOOD, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of W W WOOD, INC. in 1799 CORGEY ROAD, PLEASANTON, TX 78064 (NAICS 321999). OSHA activity number 340842426.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch W W Wood, INC. — free Get an email when a new federal OSHA severe-injury report for W W Wood, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
W W WOOD, INC.
Site address
1799 CORGEY ROAD
City
PLEASANTON
State
TX
ZIP
78064
Mailing
P.O.BOX. 398, PLEASANTON, TX 78064
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321999
Employees
115
Ownership type
A

4 citations on file for this inspection.

1910.147 C01

Other-than-serious 9 instances 11 exposed
Issued
Sep 30, 2015
Abate by
Dec 21, 2015
Penalty
Initial $6,300 · Current $5,040 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:       (a-h) Saw line section, pop-up saws 1-8: On or about August 11, 2015, and at times prior thereto, employees were exposed to hazards associated with unexpected startup while removing saw dust or replacing the cutting blade on the pop-up saws.       (i) Saw line section, chunker machine: On or about August 11, 2015, and at times prior thereto, employees were exposed to the hazards associated with unexpected startup while cleaning out the jams on the chunker machine.
Recent events (2)
  • — I (O) $5040
  • — Z (S) $6300

1910.212 A01

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Sep 30, 2015
Abate by
Oct 20, 2015
Penalty
Initial $6,300 · Current $0 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    Saw line section, pop-up saw #5: On or about August 11, 2015, and at times prior thereto, employees were exposed to a caught by hazard, while using an Ironwood pop-up saw to cut tree logs that did not have a functioning interlock switch to prevent the rotating saw blade door from opening while in operation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6300

1910.305 B01 I

Other-than-serious 1 instance 7 exposed
Issued
Sep 30, 2015
Abate by
Oct 20, 2015
Penalty
Initial $6,300 · Current $5,040 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:       Saw line section, conveyor #4: On or about August 11, 2015, and at times prior thereto, employees were exposed to an electrical hazard, while using a conveyor belt motor that had exposed 480 volt electrical conductors entering an electrical box attached to the motor.
Recent events (2)
  • — I (O) $5040
  • — Z (S) $6300

1910.305 G02 III

Other-than-serious 1 instance 7 exposed
Issued
Sep 30, 2015
Abate by
Oct 20, 2015
Penalty
Initial $6,300 · Current $5,040 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:       Saw line section, conveyor #2: On or about August 11, 2015, and at times prior thereto, employees were exposed to an electrical hazard, while using a conveyor belt motor that did not have strain relief on the 480 volt power feed cord.
Recent events (2)
  • — I (O) $5040
  • — Z (S) $6300

View W W Wood, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340842426.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.