Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RESCO PRODUCTS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of RESCO PRODUCTS, INC. in 6 CENTER STREET, TARENTUM, PA 15084 (NAICS 327125). OSHA activity number 340844497.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Resco Products, INC. — free Get an email when a new federal OSHA severe-injury report for Resco Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
6 CENTER STREET
City
TARENTUM
State
PA
ZIP
15084
Mailing
6 STREET AND CENTER STREET, TARENTUM, PA 15084
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327125
Employees
60
Ownership type
A

16 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 2 instances 10 exposed
Issued
Dec 18, 2015
Abate by
Jan 15, 2016
Penalty
Initial $3,500 · Current $2,275 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to crushed-by hazards:     a) K-Plant, press area, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, the emergency stop on a Laeis Bucher HPF 1400 hydraulic press (# 2 press) was not functional.  The emergency stop button was broken off of the panel and taped over.  Press operators and others working in the area were exposed to crushed-by hazards due to possible machine process malfunction.      b) K-Plant, press area, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, the emergency stop on a Laeis Bucher HVAKP 2000 hydraulic press (# 3 press) was not functional.  The emergency stop button was bypassed.  Press operators and others working in the area were exposed to crushed-by hazards due to possible machine process malfunction.
Recent events (2)
  • — I (S) $2275
  • — Z (S) $3500

5(a)(1)

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 18, 2015
Abate by
Jan 15, 2016
Penalty
Initial $2,800 · Current $1,820 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to being struck-by the moving components of a robotic system:      a) K-Plant, press area, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, a Schmersal brand solenoid interlock (model number: AZM-170-02ZRK) was bypassed on the barrier guard surrounding a Kukra brand robotic system (model number 125L90/2, serial number 780557) on press #2.  Employees working in the area were exposed to struck-by hazards.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.22 A02

Serious Gravity 1 2 instances 7 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $2,100 · Current $1,365 Reduced
29 CFR 1910.22(a)(2):  Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition:    a) K Plant, area behind the #1, #2, #3 and #6 presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, dust, including graphite dust, accumulated on the floor behind the presses.  The dust created a slip hazard for employees walking and operating forklifts in the area.
Recent events (2)
  • — I (S) $1365
  • — Z (S) $2100

1910.147 D03

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $3,500 · Current $2,275 Reduced
29 CFR 1910.147(d)(3): All energy isolating devices that were needed to control the energy to the machine or equipment was not physically located and operated in such a manner as to isolate the machine or equipment from the energy source:           a) K-Plant, press area, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, the hydraulic power presses were not locked out during maintenance activities including die changes and press cleaning.  Employees engaged in maintenance activities on the hydraulic presses while the presses were not locked out were exposed to crushed-by hazards.
Recent events (2)
  • — I (S) $2275
  • — Z (S) $3500

1910.303 B06

Serious Gravity 5 2 instances 7 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $3,500 · Current $2,275 Reduced
29 CFR 1910.303(b)(6): Electrical equipment were exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment:      a) K Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  On or about July 28, 2015, graphite dust accumulated on and inside of the #2 press motor control center.  The #2 press motor control cabinet was labeled as a HRC Level 4 arc flash and shock hazard.  Press operators, electricians, forklift operators, and laborers working in the area of the #2 press PLC cabinet were exposed to the hazards of arc flash, electric shock and electrocution.      b) K-Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  On or about July 28, 2015, a significant amount of graphite dust accumulated inside the '2C' panel on the #1 Press motor control cabinet.  This panel was left open due to a broken clip.  The #1 Press motor control center houses 480 volt, 3 phase conductors and was labeled as a HRC Level 4 arc flash and shock hazard.  Press operators, electricians, forklift operators, and laborers working in the area of the #1 press motor control cabinet were exposed to the hazards of arc flash, electric shock and electrocution.
Recent events (2)
  • — I (S) $2275
  • — Z (S) $3500

1910.303 B07 IV

Serious Gravity 1 2 instances 7 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect the safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:      a) K Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  On or about July 28, 2015, the #6 press motor control center had bent doors and broken disconnects.  The #6 press motor control center housed energized conductors (480 volt, 3 phase) and was labeled as a Level 0 arc flash and electric shock hazard.  Employees walking or operating forklifts next to the #6 press motor control center were exposed to electric shock hazards.    b) K Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  On or about July 28, 2015, there were broken or damaged parts on the #1 press motor control center cabinet.  The panel labeled "2C" would not stay shut due to a missing bolt.  The #1 press motor control center housed energized conductors (480 volt, 3 phase) and was labeled as a Level 4 arc flash and electric shock hazard.  Employees walking or operating forklifts next to the #6 press motor control center were exposed to electric shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 2 instances 7 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed:      a) K Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  On or about July 28, 2015, unused openings on a panel on the #1 press motor control center were not effectively closed.  The panel door labeled '#3 mix system dust collector' which was also identified by a handwritten "#3" had two open holes on the front panel.  The holes could permit the accumulation of dust, including graphite dust, inside the cabinet.  The #1 Press Motor Control Center houses 480 volt, 3 phase conductors and was labeled as a HRC Level 4 arc flash and shock hazard.  Press operators, electricians, forklift operators, and laborers working in the area of the #1 press PLC cabinet were exposed to the hazards of electric shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B08 III

Other-than-serious 1 instance 5 exposed
Issued
Dec 18, 2015
Abate by
Jan 15, 2016
Penalty
Initial $4,200 · Current $2,730 Reduced
29 CFR 1910.303(b)(8)(iii): Electric equipment provided with ventilating openings were not installed so that walls or other obstructions did not prevent the free circulation of air through the equipment:      a) K Plant, electrical panels behind the hydraulic presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, both air vents on the front of the motor control center for the #3 hydraulic press (LAEIS model number HVAKP 2000) were blocked with cardboard.  The blocked vents could result in the overheating of energized conductors (480 volt, 3 phase) housed inside the motor control center.  The cabinet was labeled as a HRC Level 0 arc flash and shock hazard.  Press operators, electricians, and laborers working in the area of the #3 press motor control center were exposed to the arc flash, electric shock, and electrocution hazards.
Recent events (2)
  • — I (O) $2730
  • — Z (S) $4200

1910.303 G01 I A

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $3,500 · Current $2,275 Reduced
29 CFR 1910.303(g)(1)(i)(A):  The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while energized was less than indicated in Table S1:    a)  K Plant, behind the #3 press, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about August 28, 2015,  the working space in front of the motor control center for the Laeis HVAKP 2000 hydraulic press (press #3) was less than indicated in Table S1.  The distance between the front of the press #3 motor control center and the pressing pumps located in front of the motor control center was approximately 2 feet.  The #3 press motor control center housed energized conductors (480 volt, 3 phase) and was listed as a HRC Level 0 arc flash and electric shock hazard.  Electricians required to perform maintenance work inside the cabinet were exposed to arc flash and electric shock hazards.
Recent events (2)
  • — I (S) $2275
  • — Z (S) $3500

1910.303 G01 VII

Serious Gravity 10 4 instances 10 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $4,900 · Current $3,185 Reduced
29 CFR 1910.303(g)(1)(vii): Switchboards, panelboards, and distribution boards installed for the control of light and power circuits, and motor control centers were not located in dedicated spaces and protected from damage:    a)  K Plant, area behind the #1, #2, and #6 presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about August 28, 2015, the motor control center for the 800 Ton Boyd mechanical power press (model Y, identified as press #6) was not located in a dedicated space that was protected from damage.  Forklifts moved hoppers within 14 inches of the #6 press motor control center on a daily basis.  Press operators, electricians, and laborers were exposed to the hazards of electric shock and electrocution.    b)  K Plant, area behind the #1, #2, and #6 presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about August 28, 2015, the motor control center for the #2 LAEIS hydraulic press (model number HPF 1400) was not located in a dedicated space that was protected from damage.  Forklifts operated in close proximity to the #2 press motor control center on a daily basis.  Press operators, electricians, and laborers were exposed to the hazards of electric shock and electrocution.    c)  K Plant, area behind the #1, #2, and #6 presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about August 28, 2015, the motor control center for the #1 LAEIS hydraulic press (model number HPF 1250) was not located in a dedicated space that was protected from damage.  Forklifts operated in close proximity to the #1 press motor control center on a daily basis.   Press operators, electricians, and laborers were exposed to the hazards of electric shock and electrocution.    d)  K Plant, area behind the #1 press, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about August 28, 2015, an electric panel marked '120/240 volt' was not located in a dedicated space and protected from damage.  The electric panel was previously damaged by a forklift which resulted in the dead front panel being knocked out of the cabinet.  Press operators, electricians, and laborers were exposed to the hazards of electric shock and electrocution.
Recent events (2)
  • — I (S) $3185
  • — Z (S) $4900

1910.305 D02

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.305(d)(2):  Panelboards that were mounted in cabinets, cutout boxes, or enclosures approved for the purpose were not of the dead-front type:      a) K-Plant, wall behind #1 Press, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, an electrical panel box (110 volt) located on a wall behind Press #1 was not equipped with a dead front.  Employees using the panel box and forklift operators passing by the panel box were exposed to the hazards of electric shock and burns.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.305 G01 IV D

Serious Gravity 5 2 instances 5 exposed
Issued
Dec 18, 2015
Abate by
Feb 1, 2016
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.305(g)(1)(iv)(D):  Flexible cords and/or cables were attached to building surfaces:      a) K Plant, #2 mixer scales near hopper of screw conveyor at #2 mixer, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, a flexible cord (110 volt) was attached to building surfaces.  The flexible cord was tied to electrical conduit at several locations along its length.  Employees working in the area, including mixing operators and mechanics, were exposed to the hazards of fire and electric shock.    b) K-Plant, next to man door beneath scales going to steps on #2 mixer, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, a flexible cord (110 volt) was attached to building surfaces.  A flexible cord used to supply power to a heat tape was tied to electrical conduit at several locations along its length.  Employees working in the area, including mixing operators and mechanics, were exposed to the hazards of fire and electric shock.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.305 G01 IV E

Serious Gravity 1 1 instance 7 exposed
Issued
Dec 18, 2015
Abate by
Feb 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(E):  Flexible cords and/or cables were concealed behind building walls, ceilings, or floors:       a) K Plant, old #1 Kiln, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, a flexible cable (220 volt, 3 phase) used to supply power to a fan was draped over the ceiling of the old #1 kiln.  The flexible cable was plugged into an outlet on the #2 kiln push control panel and was concealed by the ceiling of the old #1 kiln.  Employees working in the area, including kiln fireman and electricians, were exposed to the hazards of fire and electric shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.176 A

Repeat Gravity 5 3 instances 5 exposed
Issued
Dec 18, 2015
Abate by
Feb 29, 2016
Penalty
Initial $7,000 · Current $4,550 Reduced
29 CFR 1910.176(a): Where mechanical handling equipment was used, sufficient safe clearances were not allowed for aisles, at loading docks, through doorways and wherever turns or passage must be made, aisles and passageways were not kept clear and in good repair, with no obstruction across or in aisles that could create a hazard and permanent aisles and passageways were not appropriately marked:         a) K-Plant, behind #1, 2, 3 and 6 presses, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, sufficient safe clearances were not provided for the movement of forklifts and hoppers behind the presses.  Employees were required to move forklifts and hoppers within feet of electrical equipment including motor control centers (480 volt, 3 phase) which were labeled as HRC level 0 and level 4 arc flash and shock hazards.  Forklift operators were exposed to the hazards of electric shock and electrocution.        b)  Warehouse, between one and two rows, in front of shower room, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, a pothole existed in the warehouse floor between one and two rows.  Employees were exposed to exposed to injuries while operating forklifts over the pothole.       c) Warehouse, between eight and nine rows, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about August 28, 2015, a pothole existed in the warehouse floor between rows eight and nine.  Employees were exposed to exposed to injuries while operating forklifts over the pothole.         RESCO Products, Inc. was previously cited for this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.176(a), which was contained OSHA Inspection Number 966608, Citation #1, Item #2, and was affirmed as a final order on August 19, 2014 with respect to a jobsite located at 6th and Center Streets, Tarentum, Pennsylvania 15084.
Recent events (2)
  • — I (R) $4550
  • — Z (R) $7000

1910.303 G01 II

Other-than-serious 1 instance 5 exposed
Issued
Dec 18, 2015
Abate by
Jan 15, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii):  Working space about electric equipment rated 600 volts, nominal, or less was used for storage:                                                                  a) Maintenance Shop, next to man door leading to outside power wash area, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 31, 2015, the working space in front of electrical equipment, including the main disconnect, was used for storage.  The space directly in front of the electrical panels was used for the storage of various items including metal parts and tools.    b) Outside yard office, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, the working space in front of electrical equipment, including 480 volt switches, was used for storage.  The space directly in front of the electrical panels was used for the storage of various items including boxes, a bench, and chemical containers.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 A02 IX

Other-than-serious 1 instance 5 exposed
Issued
Dec 18, 2015
Abate by
Jan 15, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(ix):  All lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard:                                                                   a) Outside yard office, 6th and Center Streets, Tarentum, Pennsylvania 15084:  Observed on or about July 28, 2015, the light bulbs on light fixtures on the ceiling of the outside yard office were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard.  Employees working in the outside yard office were exposed to the hazards of electric shock and cuts and scrapes from broken glass in the event that the light bulbs would break.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Resco Products, INC.'s full OSHA safety record →