Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPARTMENT OF VETERAN AFFAIRS, VA ANN ARBOR HEALTHCARE SYSTEM

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF VETERAN AFFAIRS, VA ANN ARBOR HEALTHCARE SYSTEM in 2215 FULLER ROAD, ANN ARBOR, MI 48105 (NAICS 923140). OSHA activity number 340875442.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of Veteran Affairs, VA ANN Arbor Healthcare System — free Get an email when a new federal OSHA severe-injury report for Department of Veteran Affairs, VA ANN Arbor Healthcare System is published. One employer, no account, unsubscribe in one click.
Site address
2215 FULLER ROAD
City
ANN ARBOR
State
MI
ZIP
48105
Mailing
2215 FULLER ROAD, ANN ARBOR, MI 48105
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923140
Employees
1000
Ownership type
D

6 citations on file for this inspection.

1910.36 D01

Serious Gravity 5 4 instances 10 exposed
Issued
Dec 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.36(d)(1) as required by 1960.8 (b): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:   1. In building one west, on the second floor, the door leading out to the roof was locked with a dead bolt there by exposing employees to a fire hazard.  2. In the offsite warehouse, one fire exit leading out of the east side of the warehouse was locked with a deadbolt there by exposing employees to a fire hazard.  3. In the offsite warehouse, two fire exit leading out of the west side of the warehouse were locked with a deadbolt there by exposing employees to a fire hazard.
Recent events (1)
  • — Z (S) $0

1910.219 E01 I

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.219(e)(1)(i) as required by 1960.8 (b): Horizontal belts which had both runs seven feet or less from the floor level were not guarded with a guard that extended to at least fifteen inches above the belt:   In Building One West, in the sub-basement, the employer did not provide adequate guarding around horizontal belts on the Champion air compressor, Model 350.  Air Compressor is self activated and more than an eight inch section of the guarding is missing there by exposing employees to caught in hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 2 instances 5 exposed
Issued
Dec 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii) as required by 1960.8 (b): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:   a. Building One East, in the generator control room, Employees were exposed to electrical hazards in that work space in front of electrical panel was used for storage  of materials a shelving unit storing overhead light fixtures.  Employer did not provide and maintain sufficient access could hinder the ready and safe operation and maintenance of equipment.   b. Building One East, in the bank of five generator room, Employees were exposed to electrical hazards in that work space in front of electrical panels was used for storage of Such as spill response kit.  Employer did not provide and maintain sufficient access could hinder the ready and safe operation and maintenance of equipment.
Recent events (1)
  • — Z (S) $0

1910.305 A02 IX

Serious Gravity 1 3 instances 10 exposed
Issued
Dec 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(ix) as required by 1960.8 (b): All lamps for general illumination shall be protected from accidental contact or breakage by a suitable fixture or lampholder with a guard.   1. Onsite warehouse, at the loading dock, two Phoenix docklite loading lights, Model # DL-42ARM, 150 VAC, used to illuminate trailers for loading and unloading were not properly guarded to prevent accidental contact or breakage. Employees were exposed to an electrical shock hazard.   2. Offsite warehouse, at the loading dock, one Wesco incandescent dock light, no model number, used to illuminate trailers for loading and unloading were not properly guarded to prevent accidental contact or breakage. Employees were exposed to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 4, 2015
Abate by
Jan 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A) as required by 1960.8 (b): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   At the offsite warehouse, at the forklift battery charging station, a Ferro 1500 series forklift battery charger was powered using flexible cable with plug direct from the electrical panel as a substitute for fixed wiring there by exposing employees to an electrical hazard.
Recent events (1)
  • — Z (S) $0

1910.219 D01

Repeat Gravity 5 1 instance 5 exposed
Issued
Dec 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.219(d)(1) as required by 1960.8 (b): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):    In Building One West, in the sub-basement, the employer did not provide adequate guarding around on the Champion air compressor, Model 350.  Air Compressor is self activated and more than an eight inch section of the guarding is missing there by exposing employees to caught in hazards.    The Battle Creek VA Medical Center was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.219(d)(1), which was contained in OSHA inspection number 531579, citation number 2, item number 3 and was affirmed as a final order on February 11, 2013, with respect to a workplace located at 5500 Armstrong Road, Battle Creek, Michigan 49015.