Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GOODRICH CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GOODRICH CORPORATION in 50 WILLIAM WHITE BLVD, PUEBLO, CO 81001 (NAICS 336413). OSHA activity number 340882133.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Goodrich Corporation — free Get an email when a new federal OSHA severe-injury report for Goodrich Corporation is published. One employer, no account, unsubscribe in one click.
Site address
50 WILLIAM WHITE BLVD
City
PUEBLO
State
CO
ZIP
81001
Mailing
50 WILLIAM WHITE BLVD, PUEBLO, CO 81001
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336413
Employees
201
Ownership type
A

4 citations on file for this inspection.

1910.119 D02 I D

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Nov 5, 2015
Abate by
Dec 10, 2015
Penalty
Initial $4,675 · Current $0 Reduced
29 CFR 1910.119(d)(2)(i)(D): Information concerning the technology of the process did not include safe upper and lower limits for such items as temperatures, pressures, flows or compositions:   1) On August 24, 2015, and at prior times, the employers process safety information pertaining to the ethane system did not include safe upper pressure limits for the vaporizers.  Calculations for the safe upper pressure limit for the vaporizers were based on the pressure rating of a flange which was not an integral part of the vaporizer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4675

1910.119 D03 I B

Serious Gravity 5 3 instances 5 exposed
Issued
Nov 5, 2015
Abate by
Dec 10, 2015
Penalty
Initial $4,675 · Current $2,500 Reduced
29 CFR 1910.119(d)(3)(i)(B): Process safety information pertaining to the equipment in the process did not include the piping and instrument diagrams (P&ID's):      1) On August 24, 2015, and at prior times, the P&ID was inaccurate or did not represent existing equipment that was a part of the process in the following instances:      a) where the nitrogen pressure regulators for the ethane flow control valves located on the stanchions were not listed on the P&ID.      b) where the 250 psi pressure safety valves (PSV 648A and PSV 648B), located at the second state regulator panel, were labeled set at 150 psi.      c) where the nitrogen line pressure control valve (PCV 6420) was labeled set at 65 psi, which did not reflect current field settings.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4675

1910.119 L01

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Nov 5, 2015
Abate by
Dec 3, 2015
Penalty
Initial $0 · Current $0
CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process:    1) On August 24, 2105, and at prior times, the employer did not ensure that management of change was conducted for a nitrogen regulator that was installed in February 2015 on the nitrogen gas line that is used to operate the ethane flow control valves.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.119 L05

Other-than-serious 1 instance 11 exposed
Issued
Nov 5, 2015
Abate by
Dec 10, 2015
Penalty
Initial $4,675 · Current $2,500 Reduced
29 CFR 1910.119(l)(5): Where a change covered by this paragraph resulted in a change in the operating procedures or practices required by paragraph (f) of this section, the employer did not ensure that such procedures or practices were updated accordingly:    1) On August 24, 2015, and at prior times, the employer did not ensure that standard operating procedures were updated due to a required management of change in the following instance:      a) On February 24, 2014, the employer implemented a management of change related to   the installation of a temperature monitor, alarm, and transmitter for the ethane line located after the second stage regulator.  This device was installed to provide low temperature protection on the ethane system to protect the piping from any liquid ethane that might pass the vaporizers.  The employer did not ensure that standard operating procedures were updated with changes due to this new device.
Recent events (2)
  • — I (O) $2500
  • — Z (S) $4675

View Goodrich Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340882133.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.