OSHA Inspection: REG GEISMAR, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of REG GEISMAR, LLC in 36187 HWY 30, GEISMAR, LA 70734 (NAICS 325110). OSHA activity number 340902790.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch REG Geismar, LLC — free Get an email when a new federal OSHA severe-injury report for REG Geismar, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
REG GEISMAR, LLC
Site address
36187 HWY 30
City
GEISMAR
State
LA
ZIP
70734
Mailing
ATTN: PETER GUAY 36187 HWY 30, GEISMAR, LA 70734
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325110
Employees
74
Ownership type
A

3 citations on file for this inspection.

1910.119 F04

Serious Gravity 10 1 instance 4 exposed
Issued
Mar 3, 2016
Abate by
Mar 18, 2016
Penalty
Initial $70,000 · Current $7,000 Reduced

Hazardous substances 1410

29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel:    On or about September 3, 2015, at the Hydrodeoxygenator (HDO) Unit, the employer failed to implement a safe work practice which prevented employees from servicing a valve without first verifying that the locking out of a valve upstream was adequate to prevent the release of highly hazardous chemicals (hydrogen gas).
Recent events (3)
  • — C (W) $70000
  • — F (S) $7000
  • — Z (W) $70000

1910.147 C04 II

Serious Gravity 10 1 instance 4 exposed
Issued
Mar 3, 2016
Abate by
Mar 18, 2016
Penalty
Initial $0 · Current $7,000

Hazardous substances 1410

29 CFR 1910.147(c)(4)(ii): The energy control procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D):    On or about September 3, 2015, at the Hydrodeoxygenator (HDO) Unit, the employer did not ensure that written lock out/tag out procedures contained specific steps and techniques for locking out Valve 5208 or the same type of valve (solenoid) including but not limited to identifying its dual energy sources (electricity and air), how to isolate the electrical power source and its location, how to isolate the air source and its location, how to dissipate any residual electrical and air energy, and how to verify all energy sources are isolated to prevent the release of highly hazardous chemicals (hydrogen gas).
Recent events (3)
  • — C (W) $0
  • — F (S) $7000
  • — Z (W) $0

1910.147 D06

Serious Gravity 10 1 instance 4 exposed
Issued
Mar 3, 2016
Abate by
Mar 18, 2016
Penalty
Initial $0 · Current $7,000

Hazardous substances 1410

29 CFR 1910.147(d)(6): Prior to starting work on machines or equipment that had been locked out or tagged out, the authorized employee did not verify that isolation and deenergization of the machine or equipment had been accomplished:    On or about September 3, 2015, at the Hydrodeoxygenator (HDO) Unit, the employer did not ensure that an effective verification step was performed to ensure that a valve was completely isolated from hazardous energy prior to commencing work on a valve upstream to prevent the release of highly hazardous chemicals (hydrogen gas).
Recent events (3)
  • — C (W) $0
  • — F (S) $7000
  • — Z (W) $0