Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMERICAN POSTS, LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of AMERICAN POSTS, LLC in 810 CHICAGO ST., TOLEDO, OH 43611 (NAICS 332116). OSHA activity number 340909480.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch American Posts, LLC — free Get an email when a new federal OSHA severe-injury report for American Posts, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
AMERICAN POSTS, LLC
Site address
810 CHICAGO ST.
City
TOLEDO
State
OH
ZIP
43611
Mailing
810 CHICAGO ST., TOLEDO, OH 43611
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332116
Employees
15
Ownership type
A

7 citations on file for this inspection.

1910.107 C04

Serious Gravity 5 3 instances 15 exposed
Issued
Feb 8, 2016
Abate by
Mar 24, 2016
Penalty
Initial $2,000 · Current $2,000
29 CFR 1910.107(c)(4): Electrical wiring and equipment did not conform to the provisions of this paragraph and were not otherwise in accordance with subpart S of this part (Reference:  29 CFR 1910.307, Hazardous Locations):    American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that wiring and electrical equipment, including electrical outlets and light switches located inside the powder coating booth, were approved for use in a classified location for Class II dusts.  Unapproved electrical equipment can act as an ignition source, creating fire/explosion hazards.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $2000

1910.107 C07

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 8, 2016
Abate by
Mar 24, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.107(c)(7): Lamps. Electric lamps outside of, but within twenty (20) feet of any spraying area, and not separated therefrom by a partition, shall be totally enclosed to prevent the falling of hot particles and shall be protected from mechanical injury by suitable guards or by location.  American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that overhead lighting located inside the powder coating booth, were approved for use in a classified location for Class II dusts.  Unapproved electrical equipment can act as an ignition source, creating fire/explosion hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 C05

Serious Gravity 5 1 instance 15 exposed
Issued
Feb 8, 2016
Abate by
Mar 3, 2016
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.107(c)(5):  Electrical equipment not approved for locations containing both deposits of readily ignitable residues and explosive vapors was present in spraying area(s):     American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that combustible residues were cleaned from surfaces inside the paint booth.  There were visible accumulations of powder coating material on the floor, walls, and other surfaces inside the booth, posing a fire hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1910.134 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 8, 2016
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or used the respirator in the workplace:       American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that an employee using a tight-fitting ½ mask respirator while working in the powder coating booth, was medically evaluated prior to being provided with and wearing the respirator.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.134 C02 II

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 8, 2016
Abate by
Mar 24, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.134(c)(2)(ii): The employer did not establish and implement those elements of a written program necessary to ensure that any employee using a respirator voluntarily was medically able to use that respirator, and that the respirator was cleaned, stored, and maintained so that its use does not present a health hazard to the user:  American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that a written respiratory protection program was developed and implemented for the voluntary use of a tight-fitting ½ mask respirator while work was being performed in and around the powder coating booth.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 K06

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 8, 2016
Abate by
Mar 24, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.134(k)(6): The employer did not provide the basic advisory information on respirators, as presented in Appendix D of 29 CFR 1910.134, in written or oral format to employees who wear respirators when such use was not required by the employer:   American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that respiratory protection training was provided for an employee using a tight-fitting ½ mask respirator, on a voluntary bases, while working in and around the powder coating booth.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 L04 I

Other-than-serious 1 instance 15 exposed
Issued
Feb 8, 2016
Abate by
Mar 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.107(l)(4)(i): All areas were not kept free of the accumulation of powder coating dust:     American Post, LLC  Toledo, Ohio:  On or about November 30, 2015 the employer did not ensure that surfaces inside the paint booth were kept free from accumulations of powder coating dust.  There were visible accumulations of powder coating material on the floor, walls, and other surfaces inside the booth, posing a fire hazard.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View American Posts, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340909480.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.