Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SOCIAL SECURITY ADMINISTRATION-OFFICE OF DISABILITY ADJUDICATION AND REVIEW

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOCIAL SECURITY ADMINISTRATION-OFFICE OF DISABILITY ADJUDICATION AND REVIEW in 880 AVE. TITO CASTRO, SUITE 302, PONCE, PR 00716 (NAICS 923130). OSHA activity number 340962109.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Social Security Administration-Office of Disability Adjudication and Review — free Get an email when a new federal OSHA severe-injury report for Social Security Administration-Office of Disability Adjudication and Review is published. One employer, no account, unsubscribe in one click.
Site address
880 AVE. TITO CASTRO, SUITE 302
City
PONCE
State
PR
ZIP
00716
Mailing
880 AVE. TITO CASTRO, SUITE 302, PONCE, PR 00716
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923130
Employees
18
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 22 instances 18 exposed
Issued
Dec 15, 2015
Abate by
Jan 12, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:   a) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the Hearing Room #2 area, two (2) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.   b) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the Hearing Room #1 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   c) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the reception window area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  d) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the Judge's office area, two (2) relocatable power tap were not directly connected to a permanently installed branch circuit receptacle.  e) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the Group Supervisor's office area, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle.  f) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the training room area, five (5) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.  g) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the LAN room area, four (4) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.  h) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the ALJ vacant office area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  i) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the Information Technology Specialist's work area, two (2) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.  j) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the DWSA #1 area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  k) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the SCT vacant area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.  l) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the DWPA area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.304 B03 I

Serious Gravity 1 2 instances 18 exposed
Issued
Dec 15, 2015
Abate by
Jan 12, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel:   a) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the reception bathroom area, electrical receptacles were not equipped with ground-fault circuit-interrupter protection.   b) On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the female bathroom area, electrical receptacles were not equipped with ground-fault circuit-interrupter protection.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 1 exposed
Issued
Dec 15, 2015
Abate by
Jan 12, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:  On or about 9/25/15, at 880 Tito Castro Avenue, Suite 302, Ponce, PR, in the Information Technology Specialist's work area, a flexible extension cord was used in lieu of permanent wiring.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.