Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RONNYBROOK FARM DAIRY, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of RONNYBROOK FARM DAIRY, INC. in 310 PROSPECT HILL RD., ANCRAMDALE, NY 12503 (NAICS 311511). OSHA activity number 340963354.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ronnybrook Farm Dairy, INC. — free Get an email when a new federal OSHA severe-injury report for Ronnybrook Farm Dairy, INC. is published. One employer, no account, unsubscribe in one click.
Site address
310 PROSPECT HILL RD.
City
ANCRAMDALE
State
NY
ZIP
12503
Mailing
310 PROSPECT HILL RD., ANCRAMDALE, NY 12503
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311511
Employees
35
Ownership type
A

7 citations on file for this inspection.

1910.147 C01

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 8, 2016
Abate by
Apr 29, 2016
Penalty
Initial $4,900 · Current $2,300 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment was not isolated from the energy source and rendered inoperative:    A) Worksite - On or about October 5, 2015, the employer did not establish an energy control (AKA lockout/tagout) program to address maintenance employees deenergizing machinery while performing maintenance.
Recent events (2)
  • — I (S) $2300
  • — Z (S) $4900

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 8, 2016
Abate by
Apr 8, 2016
Penalty
Initial $2,800 · Current $1,600 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    A) Bottle Washer - On or about October 5, 2015, there were multiple unenclosed and unguarded parts of the Bottle Washer that could expose employees to hazards from rotating parts, specifically on the sides and front of the machine.
Recent events (2)
  • — I (S) $1600
  • — Z (S) $2800

1910.303 B07 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 8, 2016
Abate by
Mar 25, 2016
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.    A) Chemical Storage Room - On or about October 5, 2015, approximately 9 circuit breakers were missing from the electrical panel.  Eight of these openings had been covered with pieces of duct tape, which did not afford protection substantially equivalent to the walls of the panel box.  The ninth was uncovered and open.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3500

1910.303 F02

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 8, 2016
Abate by
Apr 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  A) Chemical Storage Room - On or about October 5, 2015, each circuit breaker in the Square D electrical panel was not labeled to indicate its purpose.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 I A

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 8, 2016
Abate by
Mar 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  A) Chemical Storage Room - On or about October 5, 2015, drums of chemical powder were stored in front of the electrical panels and disconnect switch.  Material should not be stored within 3 feet of this electrical equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 C03 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 8, 2016
Abate by
Mar 25, 2016
Penalty
Initial $2,800 · Current $1,600 Reduced
29 CFR 1910.303(c)(3)(i): All splices and joints and the free ends of the conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose:    A) Bottle Washer - On or about October 5, 2015, the wire to the water pump had been repaired with some wire nuts covered in electrical tape.  This did not provide insulation equivalent to that of the original conductor.
Recent events (2)
  • — I (S) $1600
  • — Z (S) $2800

1910.37 B02

Other-than-serious 1 instance 20 exposed
Issued
Mar 8, 2016
Abate by
Apr 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  A) Worksite - On or about October 5, 2015, exits were not marked with "Exit" signs throughout the establishment.