FORT GREELY, AK —
OSHA Inspection: U.S. ARMY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. ARMY in DIRECTORATE OF PUBLIC WORKS, FORT GREELY, AK 99731 (NAICS 561210). OSHA activity number 340974773.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. ARMY
- Site address
- DIRECTORATE OF PUBLIC WORKS
- City
- FORT GREELY
- State
- AK
- ZIP
- 99731
- Mailing
- IMPA-GRE-SO, PO BOX 31269, FORT GREELY, AK 99731
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 158
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.304 G05
- Issued
- Oct 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective. Carpentry shop, tool room; on or about 07 October 2015 and times prior; a 25 foot yellow extension cord was missing the ground pin. This condition exposed employees to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1910.334 A02 II
- Issued
- Oct 23, 2015
- Abate by
- Nov 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service. Carpentry shop, tool room; on or about 07 October 2015 and times prior; a yellow temporary lighting string had a damaged lamp socket. This condition exposed employees to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1910.215 A04
- Issued
- Oct 23, 2015
- Abate by
- Nov 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch. Building 615, east side; on or about 07 October 2015 and times prior thereto; the work rest on a Black and Decker Bench Grinder, serial number 896901; was not properly adjusted to a maximum of one-eighth of an inch from the abrasive wheel to the work rest. The gap between the abrasive wheel and work rest measured approximately one-quarter of an inch. This condition exposed employees to a caught in hazard. The Directorate of Public Works was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.215(a)(4), which was contained in OSHA inspection number 711238, citation number 2, item number 1 and was affirmed as a final order on 17 December 2012, with respect to a workplace located at the Build 615 Roads and Grounds Shop.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Oct 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. Plumbing shop; on or about 07 October 2015 and times prior; an energized four plug junction box was wire to an extension cord. This condition exposed employees to an electrical shock and burn hazard. The Directorate of Public Works was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 711238, citation number 2, item number 2 and was affirmed as a final order on 17 December 2012, with respect to a workplace located at the Plumbing Shop.
Recent events (1)
- — Z (R) $0
1910.305 B01 II
- Issued
- Oct 23, 2015
- Abate by
- Nov 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. Carpentry shop; on or about 07 October 2015 and times prior thereto; A knockout plug was missing from a 240 volt energized electrical junction box. Junction box supplies power to operate a table saw. This condition exposed employees to electrical shock and electrical burn hazard. The Directorate of Public Works was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(b)(1)(ii), which was contained in OSHA inspection number 711238, citation number 2, item number 3 and was affirmed as a final order on 17 December 2012, with respect to a workplace located at the Plumbing Shop.
Recent events (1)
- — Z (R) $0
More inspections at U.S. Army
View U.S. Army's full OSHA safety record →
More inspections in this industry (NAICS 561210)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340974773.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.