Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ABB, INC.

Programmed Related inspection · Safety discipline

On , OSHA opened a programmed Related safety inspection of ABB, INC. in 317 COVERED BRIDGE ROAD SW, CARTERSVILLE, GA 30120 (NAICS 238210). OSHA activity number 341024255.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ABB, INC. — free Get an email when a new federal OSHA severe-injury report for ABB, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
ABB, INC.
Site address
317 COVERED BRIDGE ROAD SW
City
CARTERSVILLE
State
GA
ZIP
30120
Mailing
2300 MECHANICSVILLE RD, FLORENCE, SC 29501
Inspection type
Programmed Related (J)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
50
Ownership type
A

3 citations on file for this inspection.

1910.269 A03 II A

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 26, 2016
Abate by
Jun 3, 2016
Penalty
Initial $5,390 · Current $5,390
29 CFR 1910.269(a)(3)(ii)(A): The contract employer did not ensure that each of its employees is instructed in the hazardous conditions relevant to the employee's work that the contract employer is aware of as a result of information communicated to the contract employer by the host employer under paragraph (a)(3)(i) of this section:    a.  Georgia Power Company, Plant Bowen JBR 3/4 Building: The ABB, Inc. company representative did not coordinate their work rules and procedures so that both Georgia Power Company and ABB, Inc. personnel were protected from shock and arc blast/flash hazards while performing circuit buss modification in Frame Cabinets , 1A and 7.
Recent events (2)
  • — I (S) $5390
  • — Z (S) $5390

1910.269 D08 II

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 26, 2016
Abate by
Jun 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(8)(ii): When servicing or maintenance is performed by a crew, craft, department, or other group, they shall use a procedure which affords the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device. Group lockout or tagout devices shall be used in accordance with the procedures required by paragraphs (d)(2)(iii) and (d)(2)(iv) of this section including, but not limited to, the following specific requirements:    a.  Georgia Power Company, Plant Bowen JBR 3/4 Building:  The crew members that were working on the circuit and equipment did not have a clearance procedure which afford each exposed employee with a level of protection equivalent to that of a personal lock to protect them from shock and arc flash/blast hazards, in that ABB failed to ensure that the Georgia Powers tagout clearance procedures, used to modify Frames 1and 1A, did not identify and controlled all energy source associated with their work.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 D08 IV

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 26, 2016
Abate by
Jun 3, 2016
Penalty
Initial $5,390 · Current $0 Reduced
29 CFR 1910.269(d)(8)(iv): Whenever outside servicing personnel are to be engaged in activities covered by paragraph (d) of this section, the on-site employer and the outside employer shall inform each other of their respective lockout or tagout procedures, and each employer shall ensure that his or her personnel understand and comply with restrictions and prohibitions of the energy control procedures being used.    a.  Georgia Power Company, Plant Bowen JBR 3/4 Building:  Prior to performing electrical circuit modification work using Georgia Power Company clearance procedures, Georgia Power Company and ABB, Inc. did not inform each other's employee representatives of their respective lockout or tagout program, procedures and policies to ensure each employee understood and complied with the restrictions and prohibitions of the energy control procedures being used.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5390

View ABB, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341024255.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.