HIGHLAND, NY —
OSHA Inspection: SELUX CORPORATION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SELUX CORPORATION in 5 LUMEN LANE, HIGHLAND, NY 12528 (NAICS 335122). OSHA activity number 341041630.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SELUX CORPORATION
- Site address
- 5 LUMEN LANE
- City
- HIGHLAND
- State
- NY
- ZIP
- 12528
- Mailing
- PO BOX 1060, HIGHLAND, NY 12528
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335122
- Employees
- 156
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.332 B01
- Issued
- Jan 19, 2016
- Abate by
- Jan 29, 2016
- Penalty
- Initial $5,400 · Current $1,620 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) Machine shop addition - On or about October, 28, 2015, an employee was directed to open an energized 75KVA transformer and was not trained by the employer concerning the hazards involved or the necessary personal protective equipment necessary to be wearing to safely work on this unit when it was energized.
Recent events (2)
- — I (S) $1620
- — Z (S) $5400
1910.333 A01
- Issued
- Jan 19, 2016
- Abate by
- Jan 25, 2016
- Penalty
- Initial $5,400 · Current $1,620 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: a) a) Machine shop addition - On or about October, 28, 2015, an employee was directed to open an energized 75KVA transformer. The employee was exposed to the possibility of burn injuries from an electrical arc flash event.
Recent events (2)
- — I (S) $1620
- — Z (S) $5400
1910.335 A01 I
- Issued
- Jan 19, 2016
- Abate by
- Jan 29, 2016
- Penalty
- Initial $5,400 · Current $1,620 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) a) Machine shop addition - On or about October, 28, 2015, an employee was directed to open an energized transformer. The employee was exposed to the possibility of burn injuries from an electrical arc flash event without adequate personal protective equipment for working on a 480 volt transformer as specified in NFPA 70 E Standards for Electric Safety in the Workplace - 2012 Edition.
Recent events (2)
- — I (S) $1620
- — Z (S) $5400
More inspections at Selux Corporation
View Selux Corporation's full OSHA safety record →
More inspections in this industry (NAICS 335122)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341041630.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.