PITTSBURGH, PA —
OSHA Inspection: CARCOLORY CORPORATION
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of CARCOLORY CORPORATION in 18 WEST STEUBEN STREET, PITTSBURGH, PA 15205 (NAICS 323111). OSHA activity number 341053379.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CARCOLORY CORPORATION
- Site address
- 18 WEST STEUBEN STREET
- City
- PITTSBURGH
- State
- PA
- ZIP
- 15205
- Mailing
- 18 WEST STEUBEN STREET, PITTSBURGH, PA 15205
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323111
- Employees
- 15
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.106 D04 I
- Issued
- Dec 24, 2015
- Penalty
- Initial $1,200 · Current $900 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(i): Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid tight raised seal or ramp at least 4 inches in height. Opening(s) from inside flammable and combustible storage room(s) were not provided with approved self-closing fire doors. The inside flammable and combustible storage room(s) were not liquid-tight where the walls joined the floor: a) In the Production Area, on or about November 10, 2015 - The opening from the inside flammable storage room into the production area was not provided with a door. Matthews Satin Mixing Base, Matthews Clear, Matthews Reducer, and Matthews Catalyst were stored in the inside storage room for two months.
Recent events (2)
- — I (S) $900
- — Z (S) $1200
1910.106 D04 III
- Issued
- Dec 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations: a) In the Production Area, on or about November 10, 2015 - The electrical panel and wiring in the inside storage room was not approved for Class I, Division 2 Hazardous Locations. Matthews Satin Mixing Base, Matthews Clear, Matthews Reducer, and Matthews Catalyst were stored in the inside storage room for two months and are category 2 and/or 3 flammable liquids.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 D04 IV
- Issued
- Dec 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(iv): Each inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system designed to provide for a complete change of air within the room at least six times per hour: a) In the Production Area, on or about November 10, 2015 - The inside storage room was not provided with an exhaust ventilation system. Matthews Satin Mixing Base, Matthews Clear, Matthews Reducer, and Matthews Catalyst were stored in the inside storage room for two months and are category 2 and/or 3 flammable liquids.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 A03
- Issued
- Dec 24, 2015
- Abate by
- Jan 7, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) In the Production Area, on or about November 10, 2015 - An exit route was obstructed by a Polar Mohr paper cutting machine.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Carcolory Corporation
View Carcolory Corporation's full OSHA safety record →
More inspections in this industry (NAICS 323111)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341053379.