Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. CHUTES CORPORATION

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of U.S. CHUTES CORPORATION in 607 BANTAM ROAD, BANTAM, CT 06750 (NAICS 332322). OSHA activity number 341072072.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Chutes Corporation — free Get an email when a new federal OSHA severe-injury report for U.S. Chutes Corporation is published. One employer, no account, unsubscribe in one click.
Site address
607 BANTAM ROAD
City
BANTAM
State
CT
ZIP
06750
Mailing
715 PARK OF COMMERCE DRIVE, BOCA RATON, FL 33487
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332322
Employees
16
Ownership type
A

6 citations on file for this inspection.

1910.151 C

Serious Gravity 5 1 instance 1 exposed
Issued
May 9, 2016
Abate by
Jun 24, 2016
Penalty
Initial $2,200 · Current $810 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  PIV BATTERY CHARGING STATION:  On or about November 19. 2015, no eye wash or quick-drenching shower was available for employees responsible for adding water to the batteries of powered industrial vehicles (PIVs).
Recent events (4)
  • — C (S) $2200
  • — F (S) $809.65
  • — Z $117586

1910.305 E02

Serious Gravity 5 1 instance 1 exposed
Issued
May 9, 2016
Abate by
Jun 24, 2016
Penalty
Initial $2,200 · Current $1,000 Reduced
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures:  PAINTING DEPARTMENT:  On or about January 6, 2016, employees were exposed to electrocution hazards as a result of an emergency eye wash that had been installed immediately below light switches that energized the lights in the paint spray booths.
Recent events (3)
  • — C (S) $2200
  • — F (S) $1000
  • — Z (S) $2200

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
May 9, 2016
Penalty
Initial $2,200 · Current $1,000 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  PIV BATTERY CHARGING STATION:  On or about November 19, 2015, the employer did not protect employees from fire by ensuring that flexible cords were connected to devices and fittings such that tension cannot be transmitted to joints or terminal screws.  The outer insulation of a flexible cord was pulled from the plug end.
Recent events (3)
  • — C (S) $2200
  • — F (S) $1000
  • — Z (S) $2200

1910.101 B

Repeat Gravity 5 2 instances 3 exposed
Issued
May 9, 2016
Penalty
Initial $3,520 · Current $1,000 Reduced
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  PRODUCTION AREA NEAR LOADING DOCK DOOR:  A)  On or about November 19, 2015, a compressed gas cylinder containing Freon 5034 was not secured and therefore was at risk of being struck by or knocked over by fork trucks and/or metal chutes/tubes or compactors that were manufactured on site (REF: CGA Pamphlet P-1-1965, Section 3.3.8).  B)  On or about January 6, 2016, a compressed gas cylinder containing carbon dioxide was not secured and therefore was at risk of being struck or knocked over by fork trucks and/or metal chutes/tubes or compactors manufactured on site and being shipped out to customers (REF: CGA Pamphlet P-1-1965, Section 3.3.8).  The employer was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 984505, citation number 1, item number 2 and was affirmed as a final order on February 4, 2015, with respect to a workplace located at 607 Bantam Road, Bantam, CT.
Recent events (3)
  • — C (R) $3520
  • — F (R) $1000
  • — Z (R) $3520

1910.134 F02

Repeat Gravity 1 1 instance 3 exposed
Issued
May 9, 2016
Abate by
Jun 24, 2016
Penalty
Initial $2,640 · Current $1,000 Reduced
29 CFR 1910.134(f)(2): Employee(s) using tight-fitting facepiece respirators were not fit tested prior to initial use of the respirator:  WELDING AREAS:  On or about November 19, 2015, employees performing TIG welding were not fit tested prior to required use of tight-fitting particulate respirators.  The employer was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 984505, citation number 2, item number 3 and was affirmed as a final order on February 4, 2015, with respect to a workplace located at 607 Bantam Road, Bantam, CT.
Recent events (4)
  • — C (R) $2640
  • — F (R) $1000
  • — Z $70554

1910.304 F01 IV

Repeat Gravity 5 1 instance 4 exposed
Issued
May 9, 2016
Abate by
Jun 24, 2016
Penalty
Initial $3,520 · Current $1,000 Reduced
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:  PRODUCTION AREA:  On or about November 19, 2015, the employer did not ensure that the working space about a 480-volt electrical panel was clear of stored items for a minimum of 42-inches and that the panels were accessible.  A)  Access to electrical panel LPL was blocked by a fork truck battery charger that was installed immediately below the panel as well as a guardrail installed 26 inches in front of the panel and forming an enclosure around the battery chargers.  The employer was previously cited for a violation of this occupational safety and health standard which was contained in OSHA inspection number 984505, citation number 1, item number 8 and was affirmed as a final order on February 4, 2015, with respect to a workplace located at 607 Bantam Road, Bantam, CT.
Recent events (3)
  • — C (R) $3520
  • — F (R) $1000
  • — Z (R) $3520