OSHA Inspection: AIR FORCE

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of AIR FORCE in 354TH LOGISTICS READINESS SQUADRON BLDG 3426, EIELSON AFB, AK 99702 (NAICS 811111). OSHA activity number 341103737.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR Force — free Get an email when a new federal OSHA severe-injury report for AIR Force is published. One employer, no account, unsubscribe in one click.
Establishment
AIR FORCE
Site address
354TH LOGISTICS READINESS SQUADRON BLDG 3426
City
EIELSON AFB
State
AK
ZIP
99702
Mailing
354 BROADWAY AVENUE SUITE 14A, EIELSON AFB, AK 99702
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
16
Ownership type
D

7 citations on file for this inspection.

1910.37 A03

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 4, 2016
Abate by
Feb 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed.   Vehicle Operations, Bldg 3425,  On or about 1 December 2015 and times prior thereto, the employer did not ensure that the exit path was clear. Snow and ice was accumulated on the exit path, reducing access width to approximately 16 inches. This condition exposed employees to delays in exiting the building and smoke inhalation and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 5 instances 10 exposed
Issued
Jan 4, 2016
Abate by
Feb 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling   LRS Vehicle Maintenance, Bldg 3315, various work stations,  On or about 1 December 2015 and times prior thereto, a 120 volt, 4-plug junction box was wired to an extension cord and connected to mechanic work stations.  This exposed employees to a 120 volt electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.303 G01 I B

Serious Gravity 1 1 instance 10 exposed
Issued
Jan 4, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater.    Vehicle Maintenance Bldg 3215  On or about 1 December 2015 and times prior thereto, electrical Panel D was blocked with shop equipment. This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 10 exposed
Issued
Jan 4, 2016
Abate by
Feb 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.  Vehicle Maintenance Bldg 3215, Transmission Bay area, On or about 1 December 2015 and times prior thereto, a 120 volt electrical outlet did not have a ground indication when tested.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 10 exposed
Issued
Jan 4, 2016
Abate by
Feb 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed  Vehicle Maintenance Bldg 3215, Transmission Bay area, On or about 1 December 2015 and times prior thereto, a 120 volt electrical panel missing knock-outs.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 4, 2016
Abate by
Feb 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings  Vehicle Operations, Bldg 3425,  On or about 1 December 2015 and times prior thereto, an 120 extension cord was routed through a door way.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 10 exposed
Issued
Jan 4, 2016
Abate by
Feb 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws   Vehicle Maintenance, Bldg 3215, Work station/tool box LGRV028, On or about 1 December 2015 and times prior thereto, an 120 volt extension cord had the insulation pulled away from the receptacle.  This condition exposed employees to and electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

View AIR Force's full OSHA safety record →