Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CAPITAL DEMOLITION LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CAPITAL DEMOLITION LLC in 25 HOLLAND AVENUE, ALBANY, NY 12209 (NAICS 238990). OSHA activity number 341131191.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Capital Demolition LLC — free Get an email when a new federal OSHA severe-injury report for Capital Demolition LLC is published. One employer, no account, unsubscribe in one click.
Site address
25 HOLLAND AVENUE
City
ALBANY
State
NY
ZIP
12209
Mailing
4456 STATE HIGHWAY 30, AMSTERDAM, NY 12010
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238990
Employees
9
Ownership type
A

5 citations on file for this inspection.

1926.150 C01 I

Deleted Serious Gravity 5 2 instances 9 exposed
Issued
Dec 23, 2015
Abate by
Jan 3, 2016
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1926.150(c)(1)(i): A fire extinguisher, rated not less than 2A, was not provided for each 3,000 square feet of the protected building area, or major fraction thereof:  (a) Main building, basement:   On or about 12/18/15, portable fire extinguishers were not provided for a protected building area of approximately 10,000 square feet; fire hazards included but were not limited to:  electrical devices, fan units, and halogen work lights.  Egress from the work are was limited due to containment enclosure.  (b) Small apartment building, east side of site:  A portable fire extinguisher was not provided for a protected building area of approximately 2000 square feet; fire hazards included but were not limited to electrical devices, halogen work lights, and kerosene.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2800

1926.151 C06

Other-than-serious 1 instance 9 exposed
Issued
Dec 23, 2015
Abate by
Jan 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.151(c)(6): Portable fire extinguishing equipment, suitable for the fire hazard(s) involved, was not provided at convenient, conspicuously accessible locations in the yard area:    (a) Front and back of main building:  On or about 12/18/15, portable fire extinguishers were not provided in area(s) where gasoline powered portable generators were in use.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1926.404 B01 II

Serious Gravity 5 3 instances 9 exposed
Issued
Dec 23, 2015
Abate by
Jan 3, 2016
Penalty
Initial $2,800 · Current $2,500 Reduced
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupers for personal protection.    (a)  Front of main building:  On or about 12/18/15, a Coleman Powermate 6875 portable generator was used for temporary 120v AC single-phase power to cord and plug connected equipment, including but not limited to:  halogen work light(s), string lights, water heater, and a skil saw; receptacles were not equipped with ground-fault circuit interrupters for shock protection.    (b)  Back of main building:  On or about 12/18/15, a Coleman Powermate 8000 and Honda EU6500is portable generator were used to provide 120v AC single-phase power to cord and plug connected equipment, including but not limited to: ventilation fans, string lights, halogen work lights; 15 and 20 Amp receptacles were not equipped with ground-fault circuit interrupters for shock protection.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $2800

1926.95 A

Other-than-serious 1 instance 3 exposed
Issued
Dec 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.95(a): Personal protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, or maintained in a sanitary and reliable condition it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation, or physical contact.  (a) Front of small building, east side:  On or about 12/18/15, employees were not using protective helmets and safety glasses while framing an OSB enclosure for a decon area; windy conditions increased the probability of a struck-by hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1926.405 A02 II E

Other-than-serious 2 instances 9 exposed
Issued
Dec 23, 2015
Abate by
Jan 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage:  (a) Main building, inside decon enclosure:  On or about 12/18/15, 500 watt halogen dual lighting fixture was not equipped with wire bulb guards, creating a burn or fire hazard.  (b) Small building, east side, basement:  On or about 12/18/15, 500 watt halogen work light was not equipped with a wire bulb guard, creating a burn or fire hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Capital Demolition LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341131191.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.