EAST GRANBY, CT —
OSHA Inspection: APPLETON GRP LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of APPLETON GRP LLC in 2 CONNECTICUT SOUTH DRIVE, EAST GRANBY, CT 06026 (NAICS 335929). OSHA activity number 341226553.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- APPLETON GRP LLC
- Site address
- 2 CONNECTICUT SOUTH DRIVE
- City
- EAST GRANBY
- State
- CT
- ZIP
- 06026
- Mailing
- 2 CONNECTICUT SOUTH DRIVE, EAST GRANBY, CT 06026
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335929
- Employees
- 29
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.212 A01
- Issued
- Mar 28, 2016
- Penalty
- Initial $3,400 · Current $0 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: Davis-Standard Extruding Line 2: On, or about, February 2, 2016, the emergency stop provided on the main operating console did not shut down the two Viteck pay-off units. In the event of an excessive amount of material paying off, employees were required to be in close proximity to the material to shut down the affected pay-off unit using the controls mounted on the side of the pay-off unit.
Recent events (3)
- — F (S) $0
- — C (S) $3400
- — Z (S) $3400
1910.303 G01
- Issued
- Mar 28, 2016
- Penalty
- Initial $3,400 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Drum Test Area: On, or about, February 2, 2016, a table that was being used as a workstation was located in the working space for Panel 10, a Square D 120/208 volt panelboard.
Recent events (3)
- — F (S) $0
- — C (S) $3400
- — Z (S) $3400
1910.333 A
- Issued
- Mar 28, 2016
- Abate by
- May 12, 2016
- Penalty
- Initial $4,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: In the following locations, on, or about, February 2, 2016, employees conducted Hi-Pot testing on spools of cable using test sets. The employer had not developed and implemented safe work procedures for high voltage testing stations. Safe work practices to protect employees from electric shock include, but are not limited to, provided insulated surfaces for the test equipment and for the employees to stand on, providing cut-out switches to disconnect test equipment from the power supply in case of an emergency and isolating the test sets and material being tested to guard against accidental contact. A. Test Area Outside of Lab. B. Kit/Packaging Area. Abatement Note: Industry guidelines provide recommendations for the safe design of electrical testing work stations.
Recent events (3)
- — F (S) $0
- — C (S) $4250
- — Z (S) $4250
1910.335 A01 I
- Issued
- Mar 28, 2016
- Abate by
- May 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: In the following locations, on or about February 2, 2016, employees who performed electrical testing on spools of cable were not provided with personal protective equipment such as, but not limited to, voltage rated gloves and fire resistive clothing: A. Test Area Outside of Lab B. Drum Test Area. C. Kit/Packaging Area. Abatement Note for Instances A and C: The use of a properly designed test area where employees are isolated from electrical hazards may eliminate the need for personal protective equipment.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.37 B02
- Issued
- Mar 28, 2016
- Abate by
- May 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": Annealing: On, or about, March 15, 2016, the doors leading from the room to an exit were not provided with an EXIT sign.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.110 C05 I I
- Issued
- Mar 28, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.110(c)(5)(i)(i): Containers, regulating equipment, manifolds, pipe, tubing, and hose were not located so as to minimize exposure to abnormally high temperatures (such as may result from exposure to convection or radiation from heating equipment or installation in confined spaces), physical damage, or tampering by unauthorized persons: Davis-Standard Extruding Line 2: On, or about February 2, 2016, a BernzOmatic cylinder with a torch attached was stored, free-standing, on the work bench.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Appleton GRP LLC
View Appleton GRP LLC's full OSHA safety record →
More inspections in this industry (NAICS 335929)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341226553.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.