OSHA Inspection: INNOVIA FILMS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of INNOVIA FILMS, INC. in 6000 SE 2ND STREET, TECUMSEH, KS 66542 (NAICS 325221). OSHA activity number 341277671.

Watch Innovia Films, INC. — free Get an email when a new federal OSHA severe-injury report for Innovia Films, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
INNOVIA FILMS, INC.
Site address
6000 SE 2ND STREET
City
TECUMSEH
State
KS
ZIP
66542
Mailing
6000 SE 2ND STREET, TECUMSEH, KS 66542
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325221
Employees
175
Ownership type
A

2 citations on file for this inspection.

1910.269 J02 III

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $4950.00 · Current $3465.00 Reduced
29 CFR 1910.269(j)(2)(iii): Live-line tools used for primary employee protection shall be removed from service every 2 years, and whenever required under paragraph (j)(2)(ii) of this section, for examination, cleaning, repair, and testing as follows:  Employee(s) using Hubbell Chance hot sticks dated October 3, 2013, Epoxiglas Hot Sticks dated June 30, 2011, and a Hastings hot stick dated March 2012 as tools for energized electrical equipment were exposed to electrical hazards due to no examination / testing being conducted every 2 years on the hot sticks.
Recent events (2)
  • — I (S) $3465
  • — Z (S) $4950

1910.303 B01 I

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $4950.00 · Current $3465.00 Reduced
29 CFR 1910.303(b)(1)(i): Electric equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees. In that, the employer's failure to consider the suitability of energized electrical equipment being exposed to water:  Water leaking from a plugged condensate pan for the Dry End HNV system would flow down the east wall of the Casting Department impacting two electrical panel boxes and a disconnect box.  The water flowing from the wall and energized electrical boxes onto the floor exposed employee(s) in the department to electrical hazards.