OSHA Inspection: RAVEN INDUSTRIES INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of RAVEN INDUSTRIES INC. in 5049 CENTER AVENUE, LATROBE, PA 15650 (NAICS 325199). OSHA activity number 341335669.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Raven Industries INC. for free Get an email when a new federal OSHA severe-injury report for Raven Industries INC. is published. One employer, no account, unsubscribe in one click.
Site address
5049 CENTER AVENUE
City
LATROBE
State
PA
ZIP
15650
Mailing
5049 CENTER AVENUE, LATROBE, PA 15650
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325199
Employees
65
Ownership type
Private (A)

9 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 12, 2016
Abate by
Aug 14, 2017
Penalty
Initial $4,900 · Current $2,450 Reduced

Hazardous substances E101E200

OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to dust explosion, deflagration, or other fire hazards as the result of working at or near dust collection systems handling combustible toner compound/additive dust which were not designed/installed/located to prevent or minimize exposure in the event of a deflagration, explosion or other uncontrolled fire event:    (a) Facility, Production Area, Latrobe, PA:  On or about 03/24/16 PVC piping was used as ductwork to collect and move combustible dust fines from the blender to the shaker during the toner making process.    (b) Facility, Production Area, Latrobe, PA:  On or 03/17/16 the Donaldson Torit collection systems installed and used on mill 1, mill 2 and classifiers 4 and 5 were located inside the building.
Recent events (2)
  • · I (S) $2450
  • · Z (S) $4900

1910.22 A01

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 12, 2016
Abate by
Aug 26, 2016
Penalty
Initial $4,900 · Current $2,450 Reduced

Hazardous substances E101E200

29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:    (a) Facility, Production Department, 5049 Center Avenue, Latrobe, PA:  On or about 03/17/16 through 03/24/16 accumulations of combustible and explosive dust generated during the toner making process had settled on equipment surfaces, structural components of equipment, beams and facility walls.
Recent events (2)
  • · I (S) $2450
  • · Z (S) $4900

1910.22 A02

Serious Gravity 5 2 instances 6 exposed
Issued
Jul 12, 2016
Abate by
Aug 26, 2016
Penalty
Initial $0 · Current $0

Hazardous substances E101E200

29 CFR 1910.22(a)(2): Floor(s) of workroom(s) were not maintained in a clean condition:    (a) Facility, Production Area, 5049 Center Drive, Latrobe, PA:  On or about 03/17/16 and 03/24/16 accumulations of combustible and explosive dust generated during the toner making process had settled on floor areas.    (b) Facility, storage area room outside production area, 5049 Center Drive, Latrobe, PA:  On or about 03/17/16 and 03/24/16 accumulations of combustible and explosive dust generated during the toner making process had settled on floor areas.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.176 C

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 12, 2016
Penalty
Initial $0 · Current $0

Hazardous substances E101E200

29 CFR 1910.176(c): Storage areas were not kept free from accumulation of materials that constituted hazards from tripping, fire, explosion or pest harborage:  (a)  Facility, Mezzanine Storage Area, 5049 Center Drive, Latrobe, PA:  On or about 03/24/16 the mezzanine storage area where dust collection filters are kept had an excessive accumulation of combustible dust and was not maintained in a clean condition.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.147 C05 II

Other-than-serious 1 instance 1 exposed
Issued
Jul 12, 2016
Abate by
Aug 26, 2016
Penalty
Initial $1,785 · Current $893 Reduced
29 CFR 1910.147(c)(5)(ii): Lockout devices and tagout devices were not singularly identified:    (a) Facility, 5049 Center Avenue, Latrobe, PA:  On or about 03/17/16 locks used by persons performing maintenance tasks were not singularly identifiable.  The employer has a lockout station that persons can go to and use any lock.  The locks are not tagged or labeled once in use to show which persons is instituting a lockout.
Recent events (2)
  • · I (O) $892.5
  • · Z (S) $1785

1910.147 C06 I

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 12, 2016
Abate by
Aug 26, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    (a) Facility, 5049 Center Avenue, Latrobe, PA:  On or about 03/17/16 the employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure the requirements of the standard were being met.  The last annual inspection of the energy control procedures was conducted 07/27/2010.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.147 C07 I

Serious Gravity 1 1 instance 6 exposed
Issued
Jul 12, 2016
Abate by
Aug 26, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees:  (a)  Facility, 5049 Center Drive, Latrobe, PA:  On or about 03/17/16 the employer has not provided training to employees to ensure the purpose and function of the energy control program was understood.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.307 C

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 12, 2016
Abate by
Sep 30, 2016
Penalty
Initial $2,380 · Current $1,190 Reduced

Hazardous substances E101E200

29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:    (a) Facility, Production Room and outer storage area, 5049 Center Drive, Latrobe, PA:  On or about 03/17/16, 03/24/16 and 06/08/16 electrical equipment subject to deposits of toner dust, a Class II combustible dust, was not dust-tight, ignition proof and approved for Class II, Division 1 locations.
Recent events (2)
  • · I (S) $1190
  • · Z (S) $2380

1910.178 L02 II

Other-than-serious 1 instance 3 exposed
Issued
Jul 12, 2016
Abate by
Aug 26, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.178(l)(2)(ii): The employer did not ensure that each operator had successfully completed the training consisting of a combination of formal instruction (e.g., lecture, discussion, interactive computer learning, video tape, written material), practical training (demonstrations performed by the trainer and practical exercises performed by the trainee), and evaluation of the operator's performance in the workplace:    (a) Facility, 5049 Center Drive, Latrobe, PA:  On or about 03/17/16 employees who operate the powered industrial trucks did not complete training that included a combination of formal instruction, practical training and evaluation of the operator's performance.  Employees participated in a formal instruction session but did not complete any practical training and evaluation.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Raven Industries INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341335669.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.