Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: AIR NATIONAL GUARD

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AIR NATIONAL GUARD in 168TH AIRCRAFT MAINTENANCE 375 TANKER ROAD, EIELSON AFB, AK 99702 (NAICS 928110). OSHA activity number 341359990.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR National Guard — free Get an email when a new federal OSHA severe-injury report for AIR National Guard is published. One employer, no account, unsubscribe in one click.
Establishment
AIR NATIONAL GUARD
Site address
168TH AIRCRAFT MAINTENANCE 375 TANKER ROAD
City
EIELSON AFB
State
AK
ZIP
99702
Mailing
375 TANKER ROAD, EIELSON AFB, AK 99702
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
104
Ownership type
D

4 citations on file for this inspection.

1910.304 F01 IV

Serious Gravity 1 2 instances 11 exposed
Issued
Apr 6, 2016
Abate by
May 4, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel.  Aircraft Maintenance; on or about 28 March 2016 and times prior thereto; the employer did not ensure that the electrical panels were readily accessible. Two instances were noted:      (a) Fabrication shop; had trash cans stored in front electrical panel labeled HA impeding access.        (b) Electrical shop; had miscellaneous items stored in front of collocated electrical panels labeled LJ-1 and LJ-2 impeding access.  This condition exposed employees to an electrical shock hazard and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 3 instances 11 exposed
Issued
Apr 6, 2016
Abate by
May 4, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Aircraft maintenance shops; on or about 28 March 2016 and times prior thereto; two instances were noted where the employer did not ensure that the electrical panels were effectively closed:      (a) Electrical shop; A 208 volt energized electrical panel board labeled L-J-2 a knockout missing on the lower left hand side of the box.      (b) Hydraulics shop; A 208 volt energized electrical panel board labeled LL had an open blank on breaker number 7.      (c) Repair and Reclamation shop; two knockouts missing on electrical box the wheel washer.   This condition exposed employees to an electrical shock, electrical burn hazards and thermal hazards.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 11 exposed
Issued
Apr 6, 2016
Abate by
May 4, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  Electrical shop; on or about 28 March 2016 and times prior thereto; and electrical outlet, on the back wall was missing a faceplate. This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.22 D01

Other-than-serious 1 instance 11 exposed
Issued
Apr 6, 2016
Abate by
May 4, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate.  Hydraulics shop mezzanine: On or about 28 March 2016 and times prior thereto, the storage area on the mezzanine did not have maximum safe load limits posted. This condition exposed employees to a struck by hazard.
Recent events (1)
  • — Z (O) $0

View AIR National Guard's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341359990.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.