OSHA Inspection: CHARLESTON AREA MEDICAL CENTER, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CHARLESTON AREA MEDICAL CENTER, INC. in 3200 MACCORKLE AVENUE, CHARLESTON, WV 25304 (NAICS 622110). OSHA activity number 341371573.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Charleston Area Medical Center, INC. — free Get an email when a new federal OSHA severe-injury report for Charleston Area Medical Center, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3200 MACCORKLE AVENUE
City
CHARLESTON
State
WV
ZIP
25304
Mailing
3200 MACCORKLE AVENUE, CHARLESTON, WV 25304
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
2500
Ownership type
A

5 citations on file for this inspection.

1926.1203 A

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 3, 2016
Abate by
Jun 15, 2016
Penalty
Initial $4,000 · Current $3,000 Reduced
29 CFR 1926.1203(a): Before it began work at a worksite, the employer did not ensure that a competent person identified each space that was a permit space, through consideration and evaluation of the elements of that space, including testing as necessary:    (a)  Ambulatory Care Building:  On or about March 30, 2016 two maintenance employees were exposed to a burn hazard when the space they entered was not classified as a permit-required confined space by a competent person prior to the work being performed.  The employees entered into a Mechanical Air Intake Pit through an approximate three foot by two foot doorway at the bottom so that one employee could cut into and relocate both a steam vent line.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1926.1207 A

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 3, 2016
Abate by
Jun 15, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.1207(a): The employer did not provide training to each employee whose work is regulated by this standard, at no cost to the employee, and did not ensure that the employee possessed the understanding, knowledge, and skills necessary for the safe performance of duties assigned under this standard:  (a)  Ambulatory Care Building:  On or about March 30, 2016 maintenance employees and management had not been trained on the additional requirements of Subpart AA Confined Spaces in Construction in that the maintenance supervisor did not know to evaluate each confined space, prior to allowing his employees to conduct construction activities, to determine if the space was a permit required confined space.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1030 H05 I A

Serious Gravity 5 8 instances 1000 exposed
Issued
Jun 3, 2016
Abate by
Jun 15, 2016
Penalty
Initial $4,000 · Current $3,000 Reduced
29 CFR 1910.1030(h)(5)(i)(A): The employer did not maintain a sharps injury log that contained at a minimum the type and brand of device involved in the incident:    (a)  Facility Wide:  On or about March 28, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.    (b)  Facility Wide:  On or about February 22, 2016 the employer did not document on the sharps injury log the type and brand of devices involved in two contaminated sharps incidents occurring on this date.    (c)  Facility Wide:  On or about February 20, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.    (d)  Facility Wide:  On or about January 28, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.    (e)  Facility Wide:  On or about January 27, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.    (f)  Facility Wide:  On or about January 17, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.    (g)  Facility Wide:  On or about January 10, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.    (h)  Facility Wide:  On or about January 8, 2016 the employer did not document on the sharps injury log the type and brand of device involved in a contaminated sharps incident occurring on this date.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.147 C04 I

Other-than-serious 1 instance 10 exposed
Issued
Jun 3, 2016
Abate by
Sep 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:    (a)  Entire Facility:  On or about March 3, 2016 equipment specific procedures were not developed for the de-energizing of equipment that did not meet the exception under this paragraph such as, but not limited to, Air Handlers that employees enter for maintenance and routine annual inspections and that have more than one energy source that requires isolation.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C06 I

Other-than-serious 1 instance 10 exposed
Issued
Jun 3, 2016
Abate by
Sep 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    (a)  Entire Facility:  On or about April 4, 2016 the employer had not conducted inspections of the energy control program at least annually to assure the procedures and requirements of the regulation were being followed.