SAN ANTONIO, TX ·
OSHA Inspection: SUNSHINE LAUNDRY, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SUNSHINE LAUNDRY, INC. in 617 N FLORES ST, SAN ANTONIO, TX 78205 (NAICS 812320). OSHA activity number 341419828.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SUNSHINE LAUNDRY, INC.
- Site address
- 617 N FLORES ST
- City
- SAN ANTONIO
- State
- TX
- ZIP
- 78205
- Mailing
- 3323 EAST COMMERCE ST., SAN ANTONIO, TX 78220
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 812320
- Employees
- 60
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.264 C04 III A
- Issued
- Jul 28, 2016
- Abate by
- Aug 7, 2016
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.264(c)(4)(iii)(a): Steam pipe(s) in laundry operations and within 7 feet of the floor or working platform, were not insulated or otherwise properly guarded to prevent contact by employees: Wash Room, on or about April 22, 2016, and at times prior thereto, employees were exposed to steam burns while walking next to an insulated steam line.
Recent events (2)
- · I (S) $1400
- · Z (S) $2800
1910.303 B02
- Issued
- Jul 28, 2016
- Penalty
- Initial $2,100 · Current $1,700 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Drain Area, on or about April 22, 2016, employees were exposed to electrical shock hazards while using a job made extension cord that was made up of a metal box with receptacle that was not used for intended purpose of being mounted securely on the wall.
Recent events (2)
- · I (S) $1700
- · Z (S) $2100
1910.305 B02 I
- Issued
- Jul 28, 2016
- Penalty
- Initial $3,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Drain Area, on or about April 22, 2016, employees were exposed to electrical shock hazards while using a job made extension cord that was made up of a metal box with receptacle on the end and no cover plate installed.
Recent events (2)
- · I (S) $0
- · Z (S) $3500
1910.303 C03 I
- Issued
- Jul 28, 2016
- Abate by
- Aug 3, 2016
- Penalty
- Initial $2,800 · Current $2,200 Reduced
General-duty citation text
29 CFR 1910.303(c)(3)(i): Conductors were not spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices were not first spliced or joined to be mechanically and electrically secure without solder and then soldered. All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose: Washer and Dryer Room, On or about April 22, 2016, and time prior thereto, employees where exposed to electrical hazards while using the pendant control on a dryer that had splices on the electrical conductor that were made with wire nuts and electrical tape.
Recent events (2)
- · I (S) $2200
- · Z (S) $2800
1910.305 G02 III
- Issued
- Jul 28, 2016
- Abate by
- Aug 3, 2016
- Penalty
- Initial $2,100 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: Washer and Dryer Room, On or about April 22, 2016, and time prior thereto, employees where exposed to electrical hazards while using the pendant control on a dryer that had a disconnected strain relief.
Recent events (2)
- · I (S) $0
- · Z (S) $2100
1910.305 G01 IV A
- Issued
- Jul 28, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Break Area, on or about April 22, 2016, employees were exposed to electrical hazards while in the break area near an extension cord that was wrapped around a metal pipe and used in a permanent fashion.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Sunshine Laundry, INC.
View Sunshine Laundry, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 812320)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341419828.