OSHA Inspection: U.S. CUSTOMS AND BORDER PROTECTION-OFFICE OF FIELD OPERATIONS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. CUSTOMS AND BORDER PROTECTION-OFFICE OF FIELD OPERATIONS in 9 N. GRAND AVENUE DECONCINI POE, NOGALES, AZ 85621 (NAICS 928120). OSHA activity number 341423929.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Customs and Border Protection-Office of Field Operations — free Get an email when a new federal OSHA severe-injury report for U.S. Customs and Border Protection-Office of Field Operations is published. One employer, no account, unsubscribe in one click.
Site address
9 N. GRAND AVENUE DECONCINI POE
City
NOGALES
State
AZ
ZIP
85621
Mailing
9 N. GRAND AVENUE ATTN: HEALTH & SAFETY-WATCH COMMANDER NORIEGA, NOGALES, AZ 85621
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928120
Employees
420
Ownership type
D

4 citations on file for this inspection.

1910.159 C10

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 15, 2016
Abate by
Aug 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained:  On or about April 22, 2016, and at times prior thereto, the employer did not ensure the minimum verticle clearance between the automatic fire sprinklers and the surface below in the following areas:   (a) Room 2212A in the Mission Support Office area, the vertical clearance between the automatic fire sprinkler and the shelf below was approximately 6 inches.  (b) Room outside kitchen in the Mission Support Office area, the vertical clearance between the automatic fire sprinkler and the shelf below was approximately 8 inches.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 15, 2016
Abate by
Aug 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about April 22, 2016, and at times prior thereto, the employer did not ensure the listed or labeled relocatable power taps were installed in accordance with instructions.   a) Room 2272 - a relocatable power tap was connected in series (daisy chained) to a second relocatable power tap to power a personal computer and monitor.
Recent events (1)
  • — Z (S) $0

1910.304 B04 II B

Serious Gravity 5 4 instances 2 exposed
Issued
Jul 15, 2016
Abate by
Aug 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4:   On or about April 22, 2016 and at times thereto, an electrical circuit was overloaded with total cord and plug connected loads in excess of Table S-4 exposing employees to electrical shock and fire hazards.     (a) Agricultural Room - An APC 15 AMP surge protector was used to power a Panasonic microwave oven (Model # NN-SN9525, 12.7 Amps), Black and Decker toaster oven (Model # TR0510TY1, 12.5 Amps) and a Mr. Coffee machine (7.5 Amps).    (b) Sentry Security Enrollment Office - A Data Guard 15 AMP surge protector was used to power a Hamilton Beach Microwave (Model # P70B20AP-G5B, 1050 watts) and a Mr. Coffee machine (Model # CG-13, 7.5 Amps).     (c) Enforcement Officer Storage Room 2206 - a QVS relocatable power tap was used to power a Magic Chef mini-refrigerator (Model # MCBR360, 1.5 AMPS) and a Rival toaster oven (Model # TO450, 12.1 Amps)     (d) Room 2272 - A Curtis SP2000 15 Amp Relocatable Power Tap was used to power a Lasko Heater (Model # 5367, 12.7 Amps)
Recent events (1)
  • — Z (S) $0

1910.157 C01

Other-than-serious 1 instance 10 exposed
Issued
Jul 15, 2016
Abate by
Aug 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a) Mission Support Lobby - A portable fire extinguisher was blocked with a trash can and located behind a pillar. Employees are trained to fight incipient level fires.
Recent events (1)
  • — Z (O) $0

View U.S. Customs and Border Protection-Office of Field Operations's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341423929.