OSHA Inspection: CAPITAL REPERTORY COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CAPITAL REPERTORY COMPANY in 111 NORTH PEARL STREET, ALBANY, NY 12207 (NAICS 711110). OSHA activity number 341494557.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Capital Repertory Company — free Get an email when a new federal OSHA severe-injury report for Capital Repertory Company is published. One employer, no account, unsubscribe in one click.
Site address
111 NORTH PEARL STREET
City
ALBANY
State
NY
ZIP
12207
Mailing
111 NORTH PEARL STREET, ALBANY, NY 12207
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
711110
Employees
20
Ownership type
A

8 citations on file for this inspection.

1910.23 A01

Serious Gravity 1 1 instance 20 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $2,138 · Current $1,069 Reduced
29 CFR 1910.23(a)(1): Every stairway floor opening was not guarded by a standard railing constructed in accordance with paragraph (e) of this section on all exposed sides (except at the entrance to the stairway):  a) Backstage Exit Area - On or about May 23, 2016, a stairway floor opening was not guarded by a standard railing exposing employees to fall hazards.
Recent events (2)
  • — I (S) $1069
  • — Z (S) $2138

1910.23 A08

Serious Gravity 1 2 instances 4 exposed
Issued
Aug 18, 2016
Abate by
Sep 7, 2016
Penalty
Initial $2,138 · Current $1,069 Reduced
29 CFR 1910.23(a)(8): Every floor hole into which persons can accidentally walk were not guarded:  a) Basement - On or about May 23, 2016, employees were exposed to caught-in and tripping hazards due to a floor hole approximately measuring 8" in length by 10" in width by 17" in depth.    b) Basement - On or about May 23, 2016, employees were exposed to caught-in and tripping hazards due to a floor hole approximately measuring 5" in length by 7" in width by 17" in depth.
Recent events (2)
  • — I (S) $1069
  • — Z (S) $2138

1910.303 B02

Serious Gravity 1 4 instances 4 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $2,138 · Current $1,069 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Basement - On or about May 23, 2016, a relocatable power tap (RPT) or power strip powering various equipment was not installed and used in accordance with instruction in the listing, labeling, or certification such as, but not limited to, daisy chaining two RPTs together that powered the various equipment.  The various equipment consisted of equipment such as, but not limited to, a microwave and toaster oven.     b) Basement - On or about May 23, 2016, the employer was using a relocatable power tap (RPT) or power strip which is not designed to for industrial use to power a microwave and toaster oven.  c) Basement - On or about May 23, 2016,  a relocatable power tap (RPT) or power strip powering various electrical equipment along with a permanent extension cord plugged into the RPT.  The permanent extension cord plugged into the RPT was then run through the ceiling over a doorway to power flood lights.
Recent events (2)
  • — I (S) $1069
  • — Z (S) $2138

1910.305 G01 IV A

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Basement - On or about May 23, 2016,  a relocatable power tap (RPT) or power strip powering various electrical equipment along with a permanent extension cord plugged into the RPT.  The permanent extension cord plugged into the RPT was then run through the ceiling over a doorway to power flood lights.  The permanent extension cord was used as permanent wiring.  b) Basement - On or about May 23, 2016, flood lights with flexible cords were used as permanent wiring and lighting throughout the basement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  a) Basement - On or about May 23, 2016,  a relocatable power tap (RPT) or power strip powering various electrical equipment along with a permanent extension cord plugged into the RPT.  The permanent extension cord plugged into the RPT was then run through the ceiling over a doorway to power flood lights
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  a) Basement - On or about May 23, 2016, the flexible cord on the flood lights had visible insulation damage to the cord set was in use.  The flexible cord on the flood lights was plugged into the permanent extension cord that was run through the ceiling over a doorway that was plugged into a relocatable power tap (RPT).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B06

Other-than-serious 1 instance 4 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a) Basement - On or about May 23, 2016, an exit sign was not illuminated.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 G01

Other-than-serious 1 instance 20 exposed
Issued
Aug 18, 2016
Abate by
Sep 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:  a) Basement - On or about May 23, 2016, employees were not trained in the use of portable fire extinguishers and the employer did not have a written fire safety policy.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0