Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PIONEER METAL FINISHING INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PIONEER METAL FINISHING INC. in 164 W 28TH AVE, OSHKOSH, WI 54902 (NAICS 332812). OSHA activity number 341532380.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pioneer Metal Finishing INC. — free Get an email when a new federal OSHA severe-injury report for Pioneer Metal Finishing INC. is published. One employer, no account, unsubscribe in one click.
Site address
164 W 28TH AVE
City
OSHKOSH
State
WI
ZIP
54902
Mailing
164 W 28TH AVE, OSHKOSH, WI 54902
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332812
Employees
55
Ownership type
A

15 citations on file for this inspection.

1910.23 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 1, 2016
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.23(a)(2): Ladderway floor opening(s) or platform(s) were not guarded by a standard railing with standard toeboard(s) on all exposed sides (except at the entrance to opening) with passage through the railing either provided with a swinging gate or so offset that a person could walk directly into the opening:      a.   E-Coat Line area work platform was not equipped with a guard for the opening at the upper landing access point 6 ft. above surface level.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.23 C01

Other-than-serious 1 instance 3 exposed
Issued
Aug 1, 2016
Abate by
Sep 20, 2016
Penalty
Initial $5,000 · Current $2,500 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toe-boards:  Note:  Toe-boards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard.    a.  In the Paint Line area, the Southern end of the work platform located above the Paint Line, at approximately 12 ft. above the surface level, did not have a top guardrail installed.    b.  In the Paint Line area, the West side of the work platform located above the Paint Line, at approximately 12 ft. above the surface level, had an unprotected edge approximately three feet long.
Recent events (2)
  • — I (O) $2500
  • — Z (S) $5000

1910.23 D01

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 1, 2016
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers was not equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section, the width of the stair to be measured clear of all obstructions except handrails:    a.  Outside the Chemical Storage area exit door, the five concrete steps up to the exit landing did not have any guardrails installed.    b.   Near the Sludge Press Area, the Waste water fixed stairway next to the control panel was not equipped with a mid-rail.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4000

1910.29 F01

Serious Gravity 5 2 instances 4 exposed
Issued
Aug 1, 2016
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.29(f)(1): "Design." Units shall comply with applicable requirements of paragraph (a) of this section.    a.  At the facility located between the Alodine line and the E-coat line, there was a mobile ladder stand that had missing castors, damaged rungs, and damaged supports.    b.  At the facility located at the side of the E-Coat line, there was a mobile ladder stand that had damaged castors, rungs, and supports.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4000

1910.107 C05

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Aug 1, 2016
Abate by
Sep 6, 2016
Penalty
Initial $5,000 · Current $0 Reduced
29 CFR 1910.107(c)(5): Electrical equipment not approved for locations containing both deposits of readily ignitable residues and explosive vapors was present in spraying area(s):   a.  In the Powder Coat Booth, a three tap extension cord was used for power to the powder coat paint equipment with paint residue covering the cord and two unused/open taps.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5000

1910.212 A01

Serious Gravity 5 1 instance 4 exposed
Issued
Aug 1, 2016
Abate by
Aug 29, 2016
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a.   The E-Coat Transfer area was not effectively guarded as it was missing a 4 ft. section of the barrier guard.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.219 C03

Serious Gravity 5 2 instances 2 exposed
Issued
Aug 1, 2016
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.219(c)(3): Vertical or inclined shafting seven -7 feet or less from floor or working platform was not enclosed with stationary casing(s):    a.  In the Southwest corner of the plant, the shaft for the Stage Washer number 10 motor was not adequately guarded.    b.  In the Southwest corner of the plant, the shaft for the Stage Washer number 11 motor was not adequately guarded.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.303 B01

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 1, 2016
Penalty
Initial $3,000 · Current $1,800 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:    a. At the facility, in the main aisle against a column an electrical receptacle box with live wiring was damaged which exposed the conductors.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3000

1910.303 E01 II

Serious Gravity 1 5 instances 2 exposed
Issued
Aug 1, 2016
Abate by
Aug 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary:  a.  In the R.O. Water Day Tank area,  the Panel LV2C switch box did not have a voltage marking.  b.  In the R.O. Water Day Tank area, the Panel HV2A 262 64 66 Stripper Tank Pump switch box did not have a voltage marking.  c.  In the R.O. Water Day Tank area, the Panel HV2 Spare switch box did not have a voltage marking.  d.  In the Alodine area, the Square D switch box did not have a voltage marking.  e.  In the Alodine area, the #2 Control box did not have a voltage marking.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Aug 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a.  On the outside of the E-Coat Motor Control Center, a damaged enclosure was mounted without a cover, which had conductors exposed at the bottom opening.  b.  In the Sludge Press area, an electrical control box had an opening which exposed the conductors.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 1, 2016
Abate by
Sep 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used to run through holes in walls, ceilings, or floors.  a.  In the Powder Coat Booth, an extension cord was ran through the wall to provide electrical power in the booth.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 3 instances 4 exposed
Issued
Aug 1, 2016
Abate by
Aug 29, 2016
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a.  In the Alodine and R.O. Water Day Tank area, live wires extending outside a conduit opening were not protected from contact by an enclosure.    b.  E-Coat Motor Controller Center had live wires on the left site of the center that were not protected from contact by an enclosure.    c.  Above the E-Coat Paint Line, the E-Coat Oven electric panel box was left open to prevent overheating exposing employees to the interior live electrical parts.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.304 G05

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 1, 2016
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a. At the facility the electrical charging plug that was equipped on the Genie GS-2032 scissor lift was missing a ground pin.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.23 A05

Other-than-serious 1 instance 2 exposed
Issued
Aug 1, 2016
Penalty
Initial $1,000 · Current $600 Reduced
29 CFR 1910.23(a)(5): Every pit was not guarded by a floor opening cover of standard strength and construction:    a. In bay 1 located in the loading dock garage there was a 16 inch sump pit that was not equipped with a cover.
Recent events (2)
  • — I (O) $600
  • — Z (O) $1000

1910.23 A08 II

Other-than-serious 2 instances 2 exposed
Issued
Aug 1, 2016
Penalty
Initial $1,000 · Current $600 Reduced
29 CFR 1910.23(a)(8)(ii): Every floor hole into which persons could accidently walk was not guarded by a floor hole cover of standard strength and construction:    a. In bay 1 located in the loading dock garage there was a 4 inch drain that was not equipped with a cover.    b. In bay 2 located in the loading dock garage there was a 4 inch drain that was not equipped with a cover.
Recent events (2)
  • — I (O) $600
  • — Z (O) $1000

View Pioneer Metal Finishing INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341532380.