Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CALIFORNIA ARMY NATIONAL GUARD

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CALIFORNIA ARMY NATIONAL GUARD in RANGE CONTROL MAINTENANCE WAREHOUSE, BLDG. 505 CAMP SAN LUIS OBISPO, SAN LUIS OBISPO, CA 93405 (NAICS 321999). OSHA activity number 341554723.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch California Army National Guard — free Get an email when a new federal OSHA severe-injury report for California Army National Guard is published. One employer, no account, unsubscribe in one click.
Site address
RANGE CONTROL MAINTENANCE WAREHOUSE, BLDG. 505 CAMP SAN LUIS OBISPO
City
SAN LUIS OBISPO
State
CA
ZIP
93405
Mailing
RANGE CONTROL MAINTENANCE WAREHOUSE, BLDG. 505 10 SONOMA AVE., CAMP SLO, SAN LUIS OBISPO, CA 93405
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321999
Employees
1
Ownership type
D

6 citations on file for this inspection.

1910.253 B04 I

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 7, 2016
Abate by
Oct 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire:  On or about June 9, 2016, welding shop, a compressed gas cylinder containing oxygen was stored in a welding tote with an acetylene gas cylinder without a regulator or cap installed on the cylinders.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 7, 2016
Abate by
Oct 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about June 9, 2016, in the warehouse, power strips were used in a work environment not described by the Underwriters Laboratories (UL) for the use of power strips, in that the employer used power strips in a wood working shop.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 7, 2016
Abate by
Oct 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure:  On or about June 9, 2016, in the office, extension cords were used to provide 120VAC service to a refrigerator and a microwave oven exposing employees to electrical shock.
Recent events (1)
  • — Z (S) $0

1910.36 E01

Repeat Gravity 5 1 instance 1 exposed
Issued
Sep 7, 2016
Abate by
Oct 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.36(e)(1): A side-hinged door was not used to connect any room to an exit route.  On or about June 9, 2016, in the warehouse, vertical rolling bay doors were designated as emergency exit doors exposing employees to fire or struck by hazards during an emergency.    The California Army National Guard was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.36(e), which was contained in OSHA inspection number 898787, citation number 1, item number 1, and was affirmed as a final order on May 9, 2013, with respect to a workplace located at Highway 101, Camp Roberts CIF Warehouse, San Miguel, CA 93451    The California Army National Guard was previously cited for a repeat violation of this occupational safety and health standard 29 CFR 1910.36(e), which was contained in OSHA inspection number 1124421, citation number 2, item number 3, and was affirmed as a final order on May 17, 2017, with respect to a workplace located at 950 N. Cucamunga Ave., Ontario, CA 91764
Recent events (1)
  • — Z (R) $0

1910.157 E02

Repeat Gravity 1 3 instances 1 exposed
Issued
Sep 7, 2016
Abate by
Oct 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  On or about June 7, 2016, fire extinguishers were not visually inspected on a monthly basis:     (a) A fire extinguisher at the west door was last visually inspected December 2014.  (b) A fire extinguisher at the center door was last visually inspected December 2014.  (c) Two fire extinguishers at the east door not have a record of monthly inspections.   The CA Army National Guard was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(e)(2) which was contained in OSHA inspection number 898511, citation number 1, item number 2, and was affirmed as a final order on May 9, 2013 with respect to a workplace located at the DPTMS, Building 101, Camp Roberts, San Miguel, CA 93451.    The CA Army National Guard was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(e)(2) which was contained in OSHA inspection number 898787, citation number 1, item number 4, and was affirmed as a final order on May 9, 2013 with respect to a workplace located at the CIF Warehouse, Camp Roberts, San Miguel, CA 93451.    The CA Army National Guard was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(e)(2) which was contained in OSHA inspection number 898988, citation number 1, item number 3, and was affirmed as a final order on May 9, 2013 with respect to a workplace located at the Range Control Office, Building 14301, Camp Roberts, San Miguel, CA 93451.
Recent events (1)
  • — Z (R) $0

1910.157 E03

Repeat Gravity 1 3 instances 1 exposed
Issued
Sep 7, 2016
Abate by
Oct 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about June 7, 2016, fire extinguisher annual maintenance checks were not conducted:   (a) The last annual maintenance check of the fire extinguisher at the west door was December 2014.  (b) The last annual maintenance check of the fire extinguisher at the center door was December 2014.    (c) Two fire extinguishers at the east door did not have a record of annual maintenance checks.    The CA Army National Guard was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(e)(3) which was contained in OSHA inspection number 898511, citation number 1, item number 3, and was affirmed as a final order on May 9, 2013 with respect to a workplace located at the DPTMS, Building 101, Camp Roberts, San Miguel, CA 93451.