OSHA Inspection: PENNSYLVANIA TRANSFORMER TECHNOLOGY INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PENNSYLVANIA TRANSFORMER TECHNOLOGY INC. in 30 CURRY AVENUE, CANONSBURG, PA 15317 (NAICS 335999). OSHA activity number 341569861.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pennsylvania Transformer Technology INC. — free Get an email when a new federal OSHA severe-injury report for Pennsylvania Transformer Technology INC. is published. One employer, no account, unsubscribe in one click.
Site address
30 CURRY AVENUE
City
CANONSBURG
State
PA
ZIP
15317
Mailing
30 CURRY AVENUE, CANONSBURG, PA 15317
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335999
Employees
312
Ownership type
A

5 citations on file for this inspection.

1910.132 A

Serious Gravity 5 1 instance 3 exposed
Issued
Jul 27, 2016
Abate by
Sep 13, 2016
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered:(a)     (a) Facility- On or about June 22, 2016, employees were positioning fall protection anchor points at their feet while working from tanks ranging from 6-15 feet fall hazards.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.132 F01

Serious Gravity 5 1 instance 3 exposed
Issued
Jul 27, 2016
Abate by
Sep 13, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.132(f)(1): The employer did not provide training to each employee who is required by this section to use personal protective equipment:  (a) Facility- On or about June 22, 2016, all employees have not received training on their personal fall arrest system that are required to wear it while working on the tanks including but not limited to the use of double lanyards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 27, 2016
Abate by
Sep 23, 2016
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    (a) Facility- On or about June 22, 2016, employees working with live electrical parts were not trained in and familiar with the safety-related work practices.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4000

1910.179 G02 II

Serious Gravity 5 1 instance 312 exposed
Issued
Jul 27, 2016
Abate by
Oct 24, 2016
Penalty
Initial $20,000 · Current $12,000 Reduced
29 CFR 1910.179(g)(2)(ii): Electrical equipment was not protected from dirt, grease, oil, or moisture:    (a) Facility- On or about June 16, 2016, rain water leaked on to the hot rails of an overhead crane leading to a small explosion and small fire.    The Pennsylvania Transformer Technology, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.179(g)(2)(ii), which was contained in OSHA inspection number 921884, citation number 1 item number 2(b) and was affirmed as a final order on 10/25/13, with respect to a workplace located at 30 Curry Avenue, Canonsburg, PA 15317.
Recent events (2)
  • — I (S) $12000
  • — Z (R) $20000

1910.305 E01

Serious Gravity 5 1 instance 312 exposed
Issued
Jul 27, 2016
Abate by
Sep 23, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:    (a) Facility, Tank Shop, Electrical Finish: On or about June 16, 2016, rain water was running onto electrical boxes that were not approved for damp and wet locations.    The Pennsylvania Transformer Technology was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(e)(1), which was contained in OSHA inspection number 921884, citation number 1, item number 2(a) and was affirmed as a final order on 10/25/13, with respect to a workplace located at30 Curry Avenue, Canonsburg, PA 15317.
Recent events (2)
  • — I (S) $0
  • — Z (R) $0

View Pennsylvania Transformer Technology INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341569861.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.