MOSS POINT, MS —
OSHA Inspection: ENTERPRISE PRODUCTS OPERATING LLC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of ENTERPRISE PRODUCTS OPERATING LLC in 6800 STENNIS BLVD, MOSS POINT, MS 39562 (NAICS 211112). OSHA activity number 341595197.
Where did this inspection happen?
- Establishment
- ENTERPRISE PRODUCTS OPERATING LLC
- Site address
- 6800 STENNIS BLVD
- City
- MOSS POINT
- State
- MS
- ZIP
- 39562
- Mailing
- P.O. BOX 4324, HOUSTON, TX 77210
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 211112
- Employees
- 30
- Ownership type
- B
Citations
3 citations on file for this inspection.
1910.119 E05
- Issued
- Abate by
- Penalty
- Initial $7126.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.119(e)(5): The employer did not assure that PHA recommendations were resolved in a timely manner (a) Cryogenic Plant, Train A - On or about August 22, 2016 Enterprise Product Partners L.P., did not have available detailed documentation of resolutions for items listed in the PHA Recommendation Action Report dated September 7, 2009. Employees were exposed to fire and explosion hazards at the aluminum exchangers which had been recommended by the PHA team to evaluate replacing H-3052/3159, H-3059/3159 exchangers with tube and sheet exchangers.
Recent events (2)
- — I (S) $0
- — Z (S) $7126
1910.119 E07
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $7126.00
General-duty citation text
29 CFR 1910.119(e)(7): The employer did not retain process hazards analyses and updates or revalidations for each process covered by this section, as well as the documented resolution of recommendations described in paragraph (e)(5) of this section for the life of the process. (a) Cryogenic Plant, Train A - On or about August 22, 2016 Enterprise Product Partners L.P., did not have available detailed documentation of resolutions for items listed in the PHA Recommendation Action Report dated September 7, 2009. Employees were exposed to fire and explosion hazards at the aluminum exchangers which had been recommended by the PHA team to evaluate replacing H-3052/3159, H-3059/3159 exchangers with tube and sheet exchangers.
Recent events (2)
- — I (O) $7126
- — Z (S) $0
1910.119 L01
- Issued
- Abate by
- Penalty
- Initial $7126.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.119(l)(1): The employer did not establish and implement written procedures to Management of Change (except for "replacements in kind") to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process. (a) Cryogenic Plant, Train A - On or about August 27, 2016 the employer did not have documentation showing that consideration, such as the technical basis for the change; it impact on employee safety and health; modification of operating procedures; time period of change and authorization for the proposed change had been address prior to changing a 4 low temp carbon steel upstream gate valve (LV 1905) for a stainless steel valve identified by eMOC 769. (b) Cryogenic Plant, Train A - On or about August 27, 2016 the employer did not have documentation showing that consideration, such as the technical basis for the change; its impact on employee safety and health; modification of operating procedures; time period of change and authorization for the proposed change had been address prior to pressure valve 58-PV5702A identified by eMOC 7750.
Recent events (2)
- — I (S) $0
- — Z (S) $7126
More inspections at ENTERPRISE PRODUCTS OPERATING LLC
LIBERTY HILL, TX—2021-09-10 00:00:00
ENTERPRISE PRODUCTS OPERATING LLC
PASADENA, TX—2016-08-02 00:00:00
ENTERPRISE PRODUCTS OPERATING LLC
CORPUS CHRISTI, TX—2014-03-11 00:00:00
ENTERPRISE PRODUCTS OPERATING LLC
BLOOMFIELD, NM—2010-06-10 00:00:00
ENTERPRISE PRODUCTS OPERATING, LLC
CLEBURNE, TX—2010-06-07 00:00:00
ENTERPRISE PRODUCTS OPERATING LLC
View ENTERPRISE PRODUCTS OPERATING LLC's full OSHA safety record →
More inspections in this industry (NAICS 211112)
MAYSVILLE, OK—2021-02-23 00:00:00
ONEOK FIELD SERVICES COMPANY, L.L.C.
WRIGHT, WY—2021-01-21 00:00:00
EOG RESOURCES, INC
HURRICANE, WV—2020-11-04 00:00:00
PILLAR ENERGY LLC
MONT BELVIEU, TX—2020-09-17 00:00:00
TARGA RESOURCES
MONT BELVIEU, TX—2020-09-16 00:00:00
S OLIVER & ASSOCIATES, LLC
More inspections in MS
LAUREL, MS—2026-07-01
THERMO-KOOL
HORN LAKE, MS—2026-07-01
NEWLY WEDS FOODS, INC.
GAUTIER, MS—2026-07-01
DOUBLE R GAUTIER, LLC
OLIVE BRANCH, MS—2026-06-30
HYVE SOLUTIONS
GAUTIER, MS—2026-06-30
STEVE WILSON ENTERPRISE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341595197.