Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: THE QUIKRETE COMPANIES, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of THE QUIKRETE COMPANIES, LLC in 541 GREEN HOLLOW ROAD, WAUREGAN, CT 06387 (NAICS 327999). OSHA activity number 341606747.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Quikrete Companies, LLC for free Get an email when a new federal OSHA severe-injury report for The Quikrete Companies, LLC is published. One employer, no account, unsubscribe in one click.
Site address
541 GREEN HOLLOW ROAD
City
WAUREGAN
State
CT
ZIP
06387
Mailing
541 GREEN HOLLOW ROAD, WAUREGAN, CT 06387
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327999
Employees
57
Ownership type
Private (A)

15 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $8,329 · Current $4,165 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to crushing hazards from a damaged lifting frame:    Q2, Reclaim:  On, or about, July 1, 2016, the lifting frame assembly that was used to suspend a fabric tote was not provided with lifting capacity for the assembly and was not subject to frequent and periodic inspections.  One of the structural members of the angle iron frame was damaged.
Recent events (3)
  • · F (S) $4165
  • · C (S) $8329
  • · Z (S) $8329

1910.184 E01

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(1): Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach:     Q2, Reclaim Platform:  On, or about, July 1, 2016, a chain alloy sling used to suspend the reclaim bag lifting frame was not provided with an identification tag.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.184 E02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(2)(i): Hooks, rings, oblong links, pear shaped links, welded or mechanical coupling links or other attachments did not have a rated capacity at least equal to that of the alloy steel chain with which they were used or the sling was used in excess of the rated capacity of the weakest component:    Q2, Reclaim Platform:  On, or about, July 1, 2016, a bolt was used to secure the lower end of a single leg sling around the shackle provided on the bag lifting frame.  The bolt had a rated capacity that was calculated to be approximately 55% of the rated capacity of the chain.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.184 E03 I

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(3)(i): A thorough periodic inspection of alloy steel chain slings was not made at least every 12 months:    Q2, Reclaim Platform:  On, or about, July 1, 2016, a single leg sling that was used to suspend the reclaim bag lifting frame was not subject to periodic, documented inspections.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.23 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $8,329 · Current $4,165 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:    Q2, Mixing Platform:  On, or about, July 13, 2016, employees were exposed to a fall hazard when they closed the gate for the hand additive pallet delivery area following a pallet delivery.
Recent events (3)
  • · F (S) $4165
  • · C (S) $8329
  • · Z (S) $8329

1910.24 E

Other-than-serious 1 instance 2 exposed
Issued
Sep 7, 2016
Penalty
Initial $4,998 · Current $2,500 Reduced
29 CFR 1910.24(e): Fixed stairs were not installed at angles to the horizontal of between 30 and 50 degrees:     Q1, Q Line:  On, or about, July 1, 2016, fixed stairs that were provided to access the palletizer transfer conveyor platform were installed at an angle of 53.3 degrees to the horizontal.
Recent events (3)
  • · F (O) $2500
  • · C (S) $4998
  • · Z (S) $4998

1910.24 G

Other-than-serious 1 instance 2 exposed
Issued
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.24(g): 29 CFR 1910.24(g): Stairway platforms were not at least the width of the stairway and 30 inches in length measured in the direction of travel:    Q1, Q Line:  On, or about, July 1, 2016, a proper landing platform had not been provided for fixed stairs  used to access the palletizer transfer conveyor platform.
Recent events (3)
  • · F (O) $0
  • · C (S) $0
  • · Z (S) $0

1910.27 B01 I

Other-than-serious Gravity 1 1 instance 2 exposed
Issued
Sep 7, 2016
Penalty
Initial $4,998 · Current $2,500 Reduced
29 CFR 1910.27(b)(1)(i): All rungs on fixed metal ladders did not have a minimum diameter of three-fourths inch:    Q1, Q Line:  On, or about, July 1, 2016, the lower access ladder was provided with rungs that were .58 inch in diameter.
Recent events (3)
  • · F (O) $2500
  • · C (S) $4998
  • · Z (S) $4998

1910.27 B01 II

Other-than-serious 1 instance 2 exposed
Issued
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.27(b)(1)(ii): The distance between rungs was not uniform throughout the ladder:    Q1, Q Line:  On, or about, July 1, 2016, the lower access ladder was not provided with uniform rung spacing.
Recent events (3)
  • · F (O) $0
  • · C (S) $0
  • · Z (S) $0

1910.27 C04

Other-than-serious 1 instance 5 exposed
Issued
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.27(c)(4): The employer did not install a fixed ladder so that the nearest permanent object in back of the ladder shall be not less than 7 inches, except when unavoidable obstructions are encountered, the ladder shall be installed with clearances as shown in figure D-3.  From figure D-3, the employer did not install the fixed ladder so that there was at least a 4 1/2 inch minimum clearance between the obstruction and the centerline of the rung just beneath the obstruction:    Q1, Q Line:  On, or about, July 1, 2016, an obstruction was located at the fourth rung on the lower access ladder.
Recent events (3)
  • · F (O) $0
  • · C (S) $0
  • · Z (S) $0

1910.147 C04 II

Other-than-serious 1 instance 2 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $6,663 · Current $3,332 Reduced
29 CFR 1910.147(c)(4)(ii): The energy control procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy:       Q1, Q Line Palletizer:  On, or about, July 1, 2016, the Lock Out/Tag Out Procedure provided for the Chantland Palletizer/Pallet Magazine did not include the potential for gravity and/or mechanical hazards created when employees were required to access the lower elevator section by walking/standing on free-wheeling conveyor rollers.
Recent events (3)
  • · F (O) $3332
  • · C (S) $6663
  • · Z (S) $6663

1910.169 B03 I

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 7, 2016
Penalty
Initial $4,998 · Current $4,998
29 CFR 1910.169(b)(3)(i): Compressed air receiver(s) were not equipped with one or more spring-loaded safety valves:     Q1, Compressor Room:  On, or about, July 1, 2016, a pressure relief valve had not been installed on the air receiver that was contained in the plants compressed air system.
Recent events (3)
  • · F (S) $4998
  • · C (S) $4998
  • · Z (S) $4998

1910.305 G01 IV A

Other-than-serious 1 instance 2 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $4,998 · Current $2,600 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Q1, Q Line:  On, or about, July 1, 2016, a metal fan that was used for general ventilation on the bagging platform was energized through a yellow extension cord.
Recent events (3)
  • · F (O) $2600
  • · C (S) $4998
  • · Z (S) $4998

1910.334 A02 II

Other-than-serious Gravity 1 1 instance 2 exposed
Issued
Sep 7, 2016
Abate by
Feb 27, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service:    Q1, Q Line:  On, or about, July 1, 2016, a yellow extension cord that was used to energize a fan on the bagging platform was damaged in that the outer jacket was cut, exposing the inner, coated conductors.
Recent events (3)
  • · F (O) $0
  • · C (S) $0
  • · Z (S) $0

1910.303 G01 II

Other-than-serious 1 instance 4 exposed
Issued
Sep 7, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:     Q1, Shrink Wrap Area:  On, or about, July 1, 2016, a plastic barrel and a portable fan was stored in front of the GE 120/208 volt panel.
Recent events (3)
  • · F (O) $0
  • · C (O) $0
  • · Z (O) $0

View The Quikrete Companies, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341606747.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.