Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VETERANS ADMINISTRATION MEDICAL CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VETERANS ADMINISTRATION MEDICAL CENTER in 940 BELMONT STREET, BROCKTON, MA 02301 (NAICS 622210). OSHA activity number 341673747.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Veterans Administration Medical Center — free Get an email when a new federal OSHA severe-injury report for Veterans Administration Medical Center is published. One employer, no account, unsubscribe in one click.
Site address
940 BELMONT STREET
City
BROCKTON
State
MA
ZIP
02301
Mailing
940 BELMONT STREET, BROCKTON, MA 02301
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622210
Employees
1500
Ownership type
D

9 citations on file for this inspection.

1910.23 B01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.23(b)(1)(i): Rail, roller, picket fence, half door or equivalent barrier was not provided on the opening for handling materials, the guards were not kept in position regardless of a door on the opening.  In addition there were not grab handles provided on each side of the opening with its center approximately 4 feet above floor level and of standard strength and mounting.  Building 3 mechanical room, Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016, employees were exposed to unprotected falls of approximately 12 feet while standing on the edge of the wall opening of the mechanical room while moving a pump and after the process was complete.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.101 B

Serious Gravity 5 1 instance 6 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  Welding building, Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016, an oxygen cylinder was stored in the welding building without being secured to prevent falling per the Compressed Gas Association Pamphlet P-1-1965.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 22, 2016
Abate by
Nov 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  Building 69 Generator, Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016 the alternator and alternator belts on the emergency generator were not guarded to protect employees from rotating fans and the in-running nip points on the belts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A03 II

Serious Gravity 10 2 instances 25 exposed
Issued
Sep 22, 2016
Abate by
Nov 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(3)(ii): Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle:   Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016 point of operation guards were not provided to prevent employees from having any parts of their bodies from entering into the danger zone while the machine was in operation.  a.  The Groen Direct-Steam Mixer Kettle did not have a cover to prevent employees from coming into contact with the hot water inside the kettle and within 2 inches from the rim of the kettle as the agitator rotated inside.  b.  The JET Milling/Drilling machine in the Welding Building did not have a point of operation guard to prevent employees from coming into contact with the bit during operation.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.253 B04 I

Serious Gravity 5 1 instance 6 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire;  Welding room, Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016, oxygen cylinders were stored adjacent to liquid petroleum gas (LPG) cylinders.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Building 4, 1-B Café, Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016, the employer provided an extension cord for use in the 4-1-B café where a junction box with knockouts was used to house the outlets.  The box is designed to be wall mounted and not in a wet location.  The cord has been set in a pool of water in the past that has collected under the steam tables.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 3 instances 10 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or before August 3, 2016, employees were exposed to electrical shock hazards as live parts of electrical equipment operating at 50 volts or more were not guarded against accidental contact.  a.  Building 4 penthouse - elevator control cabinets operating at 480 volts were left open b.  Switchgear room -  Battery charging section of the switchgear had exposed electrical parts operating at 54 volts DC c.  Building 7 mechanical room - the door to the building controls cabinet with exposed 120 volt conductors was left open
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 A01

Other-than-serious 2 instances 30 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.  Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016, employee work areas were not kept in an orderly or sanitary condition.  a.  Mechanical room, building 1, drink bottles and food wrappers were on the floor creating a slip, trip, and fall hazard. b.  Laundry, lower level on the soiled laundry side, drink bottles and food wrappers were on the floor in a potentially contaminated area creating an unsanitary condition.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.146 D01

Other-than-serious 4 instances 6 exposed
Issued
Sep 22, 2016
Abate by
Oct 21, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.146(d)(1): Under the permit-required confined space program required by 29 CFR 1910.146(c)(4), the employer did not implement the measures necessary to prevent unauthorized entry:  Brockton VA Hospital, 940 Belmont Street, Brockton, Massachusetts; On or about August 3, 2016, permit required confined spaces were not secured to prevent unauthorized entry.  a.  Pool building mechanical room (2) b.  Building 1 mechanical room c.  Building 3 mechanical room
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Veterans Administration Medical Center's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341673747.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.