AUSTIN, TX —
OSHA Inspection: KIM'S CLEANERS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of KIM'S CLEANERS in 4201 WESTBANK DRIVE, AUSTIN, TX 78746 (NAICS 812320). OSHA activity number 341692358.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KIM'S CLEANERS
- Site address
- 4201 WESTBANK DRIVE
- City
- AUSTIN
- State
- TX
- ZIP
- 78746
- Mailing
- 4201 WESTBANK DRIVE, AUSTIN, TX 78746
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 812320
- Employees
- 30
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.145 C03
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $3,741 · Current $1,232 Reduced
General-duty citation text
29 CFR 1910.145(c)(3): Safety instruction sign(s) were not used where there was a need for general instructions and suggestions relative to safety measure(s): On or about August 12, 2016, and at times prior thereto, the employer did not post signs warning on clearance limit on or under the cloths racking systems. Employees had to bend over and walk under the racks and could strike their heads.
Recent events (2)
- — I (S) $1232
- — Z (S) $3741
1910.264 C04 III A
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $3,741 · Current $1,232 Reduced
General-duty citation text
29 CFR 1910.264(c)(4)(iii)(a): Steam pipe(s) in laundry operations and within 7 feet of the floor or working platform, were not insulated or otherwise properly guarded to prevent contact by employees: On or about August 12, 2106, and at times prior thereto, the employer did not ensure that the steam pipes located in the boiler room were guarded to prevent contact, exposing employees to the hazard of hot surfaces.
Recent events (2)
- — I (S) $1232
- — Z (S) $3741
1910.303 B02
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $3,741 · Current $1,232 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. On or about August 12, 2016, and at times prior thereto, the employer did not ensure that electrical equipment was installed and used in accordance with any instructions included in the listing and labeling in three instances in the dry cleaning shop, exposing employees to the hazard of electrical shock and burns. a. In the boiler room a six plug surge protector was being used as permanent wiring system. b. In the boiler room an orange 3 plug receptacle was being used as permanent wiring system. c. In the dry cleaning area behind the dry cleaning machine a six plug receptacle was being used as permanent wiring system.
Recent events (2)
- — I (S) $1232
- — Z (S) $3741
1910.303 B07 IV
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There was damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: On or about August 12, 2016, and at times prior thereto, the employer did not ensure that damaged parts in 2 instances throughout the facility were kept in a safe operating condition, exposing employees to the hazard of electrical shock. a. In the boiler room the 240 volt conduit running to the boiler controls was broken and bent, the wire were exposed on the inside. b. In the dry cleaning area on the wall behind the dry cleaning machines the wall was rotten and deteriorating and the electrical receptacle was loose.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about August 12, 2016, and at times prior thereto, the employer did not ensure that each breaker in the breaker box located in the end plate department was marked to indicate its purpose.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about August 12, 2016, and at times prior thereto, the employer was storing a commercial clothes dryer in front of two electrical breaker panels, blocking the access to the panels.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $3,741 · Current $1,233 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about August 12, 2016, in the Cloths Storing Area the toggle switch receptacle outlet box for the cloths conveyor system was missing a knock outs on the back and side of the box, exposing employees to the hazards of electrical shock.
Recent events (2)
- — I (S) $1233
- — Z (S) $3741
1910.305 B02
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about August 12, 2016, and at times prior thereto, the outlet box next to the door in the boiler room was missing the cover, exposing employees to the hazard of electrical shock.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Oct 7, 2016
- Abate by
- Oct 17, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords were being used as a permanent source for wiring: On or about August 12, 2016, and at times prior thereto, flexible cords were being used a permanent wiring in 3 instances. a. In the iron press area on the on the hand iron control box an orange extension cord had been hard wired into the control box. b. In the stream area on the blue Ajax "Susie" Steamer an orange extension cord had been hard wired into the control box. c. In the stream area on the yellow Ajax "Susie" Steamer an orange extension cord had been hard wired into the control box.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Kim'S Cleaners
View Kim'S Cleaners's full OSHA safety record →
More inspections in this industry (NAICS 812320)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341692358.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.