OSHA Inspection: HAO INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HAO INC. in 209 EAST HARMON INDUSTRIAL PARK UNIT 1E-A, TAMUNING, GU 96913 (NAICS 444190). OSHA activity number 341721967.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch HAO INC. — free Get an email when a new federal OSHA severe-injury report for HAO INC. is published. One employer, no account, unsubscribe in one click.
Establishment
HAO INC.
Site address
209 EAST HARMON INDUSTRIAL PARK UNIT 1E-A
City
TAMUNING
State
GU
ZIP
96913
Mailing
209 EAST HARMON INDUSTRIAL PARK RD UNIT 1E-A, TAMUNING, GU 96913
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
444190
Employees
9
Ownership type
A

14 citations on file for this inspection.

1910.303 B01

Serious Gravity 1 2 instances 4 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $2,138 · Current $1,497 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):  (a) At the Hydra Air Pacific, the Dayco and NRP Jones hose crimpers did not have their incandescent lamps in their lamp holders exposing bare circuit when the equipment are energized.
Recent events (2)
  • — I (S) $1496.6
  • — Z (S) $2138

1910.305 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  (a) At the Hydra Air Pacific, the main electrical power panel top right hand circuit breaker did not have filler plates exposing the buss bar.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 2 instances 3 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  (a) At the Hydra Air Pacific, yellow extension cord were used to extend power to shop equipment for more than 90 days.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 1 2 instances 3 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows, or similar openings  (a) At the Hydra Air Pacific, yellow extension cords used to extend power to the warehouse and office equipment were run through doorways and windows.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 2 instances 3 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces.  (a) At the Hydra Air Pacific, yellow extension cord were used to extend power to shop equipment were attached to building surfaces.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 II

Serious Gravity 1 1 instance 3 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap.  (a) At the Hydra Air Pacific, red extension cord used to extend power to the Brake quip auto plumbing hose crimper was repaired and taped.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 28, 2016
Abate by
Nov 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws.  (a) At the Hydra Air Pacific warehouse area, the orange power cord of the hose crimper did not have strain relief, insulation was separating from the plug.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 D01

Other-than-serious 1 instance 1 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate.  (a) At the Hydra Air Pacific Guam warehouse, the mezzanine floor used for materials and parts storage did not have the maximum load limit posted in a conspicuous place.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.36 G02

Other-than-serious 1 instance 1 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  (a) At the Hydra Air Pacific Manager's Office, exit access was reduced to 25 inches wide, obstructed by white file cabinet.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.101 B

Other-than-serious 2 instances 4 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b):   Compressed gas cylinder(s) not in use were not properly supported to prevent them from being knocked over:  (a) At the Hydra Air Pacific, oxygen and acetylene gas cylinders in storage were not properly secured.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E02

Other-than-serious 4 instances 5 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable extinguishers or hose used in lieu thereof under paragraph (d)(3) of this section were not visually inspected monthly.  (a) At the Hydra Air Pacific, portable fire extinguishers were not visually inspected monthly, last inspection date was June 2016.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.212 A01

Other-than-serious 1 instance 1 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  (a) At the Hydra Air Pacific, the Jet Drill press was used without a guard installed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.215 B09

Other-than-serious 1 instance 1 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch.  (a) At the Hydra Air Pacific, the 10 inch Jet Equipment tools bench grinder was used with its abrasive wheel and the tongue guard adjusted to 2 inches.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.253 B04 III

Other-than-serious 1 instance 4 exposed
Issued
Oct 28, 2016
Abate by
Nov 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour.  (a) At the Hydra Air Pacific, oxygen and acetylene gas cylinders in storage were not separated a minimum distance of 20 feet.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View HAO INC.'s full OSHA safety record →