LINN, MO —
OSHA Inspection: QUALITY CUSTOM MOLDING LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of QUALITY CUSTOM MOLDING LLC in 209 WEST MAIN ST., LINN, MO 65051 (NAICS 326199). OSHA activity number 341735454.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- QUALITY CUSTOM MOLDING LLC
- Site address
- 209 WEST MAIN ST.
- City
- LINN
- State
- MO
- ZIP
- 65051
- Mailing
- 209 WEST MAIN ST., LINN, MO 65051
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 30
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.304 G05
- Issued
- Sep 26, 2016
- Abate by
- Oct 21, 2016
- Penalty
- Initial $3,180 · Current $2,226 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: Instances existed of missing ground pins on operating equipment, such as, but not limited to, cooling fans in areas BM3 and BM8, exposing employees to an electrical shock. Abatement documentation is required for this violation.
Recent events (2)
- — I (O) $2226
- — Z (S) $3180
1910.305 G02 III
- Issued
- Sep 26, 2016
- Abate by
- Oct 21, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: There was no strain relief (damage to cord insulation at the plug) for a 110 V cooling fan in BM1, potentially exposing employees to an electrical shock. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Quality Custom Molding LLC
View Quality Custom Molding LLC's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341735454.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.