INARAJAN, GU —
OSHA Inspection: DZSP 21 LLC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of DZSP 21 LLC in FENA POTABLE WATER TREATMENT PLANT BLDG. 576, INARAJAN, GU 96915 (NAICS 221310). OSHA activity number 341741148.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DZSP 21 LLC
- Site address
- FENA POTABLE WATER TREATMENT PLANT BLDG. 576
- City
- INARAJAN
- State
- GU
- ZIP
- 96915
- Mailing
- P.O. BOX GH, HAGATNA, GU 96932
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221310
- Employees
- 91
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.119 D
- Issued
- Oct 12, 2016
- Abate by
- Jan 31, 2017
- Penalty
- Initial $6,057 · Current $4,240 Reduced
General-duty citation text
29 CFR 1910.119(d): The employer did not complete a compilation of written process safety information, including information pertaining to the hazards of the highly hazardous chemicals used or produced by the process, information pertaining to the technology of the process, and information pertaining to the equipment in the process before conducting the process hazard analysis: (a) On August 22, 2016 at the Fena Water Treatment Plant, the employer did not compile current Process Safety Information (PSI) pertaining to use of a 1-ton Chlorine Cylinder in the chlorination system, prior to relocating a one-ton chlorine cylinder from the Fena Pump Station to the Fena Water Treatment Plant.
Recent events (2)
- — I (S) $4239.9
- — Z (S) $6057
1910.119 E06
- Issued
- Oct 12, 2016
- Abate by
- Jan 31, 2017
- Penalty
- Initial $6,057 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(e)(6): The process hazard analysis was not updated and revalidated every five years: (a) On August 22, 2016 at the Fena Water Treatment Plant, the employer did not update existing safety and health procedures every 5 years for use of a 1-ton Chlorine cylinder for the chlorination system. The last update was conducted on February 15, 2008.
Recent events (2)
- — I (S) $0
- — Z (S) $6057
1910.119 F01
- Issued
- Oct 12, 2016
- Abate by
- Oct 20, 2016
- Penalty
- Initial $6,057 · Current $4,240 Reduced
General-duty citation text
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information: (a) On August 22, 2016 at the Fena Water Treatment Plant, operating procedures were not developed to instruct operators on the use of 1-ton Chlorine cylinders as back-up for the chlorination system.
Recent events (2)
- — I (S) $4239.9
- — Z (S) $6057
1910.119 F01 I C
- Issued
- Oct 12, 2016
- Abate by
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(1)(i)(C): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting temporary operations: (a) On August 22, 2016 at the Fena Water Treatment Plant, temporary operating procedures were not developed to address the hazards of using a 1-ton Chlorine cylinder as a temporary back-up for the chlorination system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F03
- Issued
- Oct 12, 2016
- Abate by
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(3): The operating procedures were not reviewed to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities. (a) On August 22, 2016 at the Fena Water Treatment Plant, a 1-ton Chlorine Cylinder was relocated to the Fena water treatment Plant without updating current procedures to reflect current operating practices.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 G01 I
- Issued
- Oct 12, 2016
- Abate by
- Oct 20, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(g)(1)(i): The employer did not train each employee before being involved in operating a newly assigned process in the operating procedures as specified in paragraph (f) of this section. (a) On August 22, 2016 at the Fena Water Treatment Plant, the employer did not train affected employees on the process to use a 1-ton chlorine cylinder as a backup for the chlorination system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 L01
- Issued
- Oct 12, 2016
- Abate by
- Oct 20, 2016
- Penalty
- Initial $6,057 · Current $4,240 Reduced
General-duty citation text
29 CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process. (a) On August 22, 2016 at the Fena Water Treatment Plant, the employer did not establish and implement written procedures to manage changes to the operation pertaining to the chlorination system.
Recent events (2)
- — I (S) $4239.9
- — Z (S) $6057
More inspections at Dzsp 21 LLC
View Dzsp 21 LLC's full OSHA safety record →
More inspections in this industry (NAICS 221310)
More inspections in GU
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341741148.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.