Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EATON CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of EATON CORPORATION in 1725 1200TH AVE, LINCOLN, IL 62656 (NAICS 335313). OSHA activity number 341747731.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Eaton Corporation — free Get an email when a new federal OSHA severe-injury report for Eaton Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
EATON CORPORATION
Site address
1725 1200TH AVE
City
LINCOLN
State
IL
ZIP
62656
Mailing
1725 1200TH AVE, LINCOLN, IL 62656
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335313
Employees
700
Ownership type
A

3 citations on file for this inspection.

1910.36 G02

Deleted Serious Gravity 1 1 instance 10 exposed
Issued
Dec 23, 2016
Penalty
Initial $4,543 · Current $0 Reduced
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  On or about August 29, 2016 maintenance employees were expected to access the electrical cabinets that serviced the AIDA Caseline machine and were exposed to hazards that related to exiting the building.  The employer did not ensure that exit pathways were maintained at 28 inches or more at all times; the exit paths from the electrical cabinets were approximately 16 inches at one end and 21 inches at the other end.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4543

1910.303 G01 I A

Deleted Serious Gravity 5 1 instance 10 exposed
Issued
Dec 23, 2016
Penalty
Initial $7,572 · Current $0 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:  On or about August 29, 2016 employees required to access and service the AIDA endwall press electrical cabinet were exposed to electrical injuries and the rear cabinet doors were blocked by a guardrail that had been installed approximately 12.75 inches away.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7572

1910.303 G01 I B

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 23, 2016
Penalty
Initial $0 · Current $2,000
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the working space did not permit at least a 90-degree opening of equipment doors or hinged panels:    On or about August 29, 2016 employees required to access and service the AIDA endwall press electrical cabinet were exposed to a shock hazard and the rear cabinet doors were blocked by a guardrail and did not allow the doors to open at least 90 degrees.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $0

View Eaton Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341747731.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.