Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SELECT INDUSTRIES, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of SELECT INDUSTRIES, INC. in 420 S CASCADE ST, NEW CASTLE, PA 16101 (NAICS 323111). OSHA activity number 341818375.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Select Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Select Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
420 S CASCADE ST
City
NEW CASTLE
State
PA
ZIP
16101
Mailing
P.O. BOX 7158, NEW CASTLE, PA 16107
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323111
Employees
15
Ownership type
A

7 citations on file for this inspection.

1910.106 D04 I

Serious Gravity 5 1 instance 14 exposed
Issued
Dec 8, 2016
Abate by
Jul 10, 2017
Penalty
Initial $6,236 · Current $4,490 Reduced
29 CFR 1910.106(d)(4)(i): Opening(s) from inside flammable and combustible storage room(s) were not provided with approved self-closing fire doors:      a) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto, the opening, from inside the flammable storage room to the shipping/production area, was not provided with an approved self-closing fire door. No door was installed at the opening.
Recent events (3)
  • — P (S) $4490
  • — I (S) $4490
  • — Z (S) $6236

1910.106 D04 II

Serious Gravity 5 1 instance 15 exposed
Issued
Dec 8, 2016
Abate by
Mar 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(ii): Storage in inside storage rooms did not comply with Table H-13.    a) Select Industries, Inc., Flammable Liquid Storage Room - On or about October 5, 2016, and at times prior thereto, the quantity of flammable liquids stored in the room exceeded the allowable quantity, as listed in 29 CFR 1910.106 Table H-13. Approximately 5115 gallons of flammable liquids were stored in the inside flammable storage room.  The room was approximately 704 sq ft.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 D04 III

Serious Gravity 5 1 instance 14 exposed
Issued
Dec 8, 2016
Abate by
Mar 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations:     a) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto, lights installed in the inside flammable storage room, used for Category 1, Category 2, and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were not approved for the location.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 D04 IV

Serious Gravity 5 1 instance 15 exposed
Issued
Dec 8, 2016
Abate by
Mar 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(iv): Each inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system designed to provide for a complete change of air within the room at least six times per hour.       a) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto, the flammable liquid storage room was not provided with an exhaust ventilation system.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 D04 V

Serious Gravity 5 1 instance 15 exposed
Issued
Dec 8, 2016
Abate by
Mar 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(v): A clear aisle at least 3 feet wide was not maintained in inside storage rooms and containers over 30 gallons capacity were stacked one upon the other.     a) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto, a clear aisle at least 3 feet wide was not maintained in the flammable liquid storage room, as required.      b) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto, 55 gallon drums of flammable liquids, stored in the flammable liquid storage room,  were stacked one upon the other.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 1 1 instance 14 exposed
Issued
Dec 8, 2016
Abate by
Jul 10, 2017
Penalty
Initial $3,741 · Current $1,500 Reduced

Hazardous substances 056024602590

29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    a) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto: Employees worked with and around hazardous substances including, but not limited to, Carbon monoxide, Toluene, Acetone, and Isopropanol.  Employer did not develop and implement a written hazard communication program.
Recent events (3)
  • — P (S) $1500
  • — I (S) $1500
  • — Z (S) $3741

1910.1200 H01

Serious Gravity 1 4 instances 14 exposed
Issued
Dec 8, 2016
Abate by
Mar 13, 2017
Penalty
Initial $0 · Current $0

Hazardous substances 056024602590

29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:    a) Select Industries, Inc. - On or about October 5, 2016, and at times prior thereto: Employees worked with and around hazardous substances including, but not limited to, Carbon monoxide, Toluene, Acetone, and Isopropanol.  Employees were not provided effective information and training on hazards of the chemicals in the work area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Select Industries, INC.'s full OSHA safety record →