Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GREAT LAKES POLYMER TECHNOLOGIES, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GREAT LAKES POLYMER TECHNOLOGIES, LLC in 100 S. FABPRO WAY, KINGMAN, KS 67068 (NAICS 314991). OSHA activity number 341836799.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Great Lakes Polymer Technologies, LLC — free Get an email when a new federal OSHA severe-injury report for Great Lakes Polymer Technologies, LLC is published. One employer, no account, unsubscribe in one click.
Site address
100 S. FABPRO WAY
City
KINGMAN
State
KS
ZIP
67068
Mailing
100 S. FABPRO WAY, KINGMAN, KS 67068
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
314991
Employees
150
Ownership type
A

5 citations on file for this inspection.

1910.303 B01

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 28, 2016
Abate by
Dec 22, 2016
Penalty
Initial $12,471 · Current $6,236 Reduced
29 CFR 1910.303(b)(1):     Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations:
Recent events (2)
  • — I (S) $6235.5
  • — Z (S) $12471

1910.303 G02 I B

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Nov 28, 2016
Abate by
Dec 22, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i)(B): Except as elsewhere required or permitted by this standard, live parts of electrical equipment operating at 50 volts or more was not guarded by suitable permanent, substantial partitions or screens so arranged so that only qualified persons would have access to the space within reach of the live parts. Any openings in such partitions or screens were not so sized and located that persons were not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them:  On or about 5 Oct 2016 - Employees engaged in the die changed activities on the extrusion machine line 1 were exposed to electrical hazards in that guards were not provided to protect against exposed heating element connections.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A01

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Nov 28, 2016
Abate by
Dec 22, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  On or about 5 Oct 2016 - Employees engaged in the die changed activities on Reifenhauser extrusion machine Line 1 were exposed to electrical hazards in that exposed heating element wires were not de-energized prior to work being performed in close proximity of exposed wires.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 L04 I

Serious Gravity 1 1 instance 1 exposed
Issued
Nov 28, 2016
Abate by
Dec 22, 2016
Penalty
Initial $5,345 · Current $2,673 Reduced
29 CFR 1910.178(l)(4)(i): Refresher training, including an evaluation of the effectiveness of that training, was not conducted as required by paragraph (l)(4)(ii) to ensure that the operator had the knowledge and skills needed to operate the powered industrial truck safely:  Employees engaged in forklift operation activities in the production area were exposed to struck-by hazards in that forklift refresher training had not been completed.
Recent events (2)
  • — I (S) $2672.5
  • — Z (S) $5345

1910.305 G02 III

Serious Gravity 1 3 instances 3 exposed
Issued
Nov 28, 2016
Abate by
Dec 22, 2016
Penalty
Initial $5,345 · Current $2,673 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:     Employees engaged in the extrusion process on line 1 were exposed to electrical shock hazards in that strain relief components are not provided on equipment located near extrusion operating area.    a) At the Oil heater set of Roll for the Reifenhauser Extruder machine Line 1.  b) At the work lamp above the green heater in Line 1.  c) At the Roll Stand Emergency Stop Bar for Line 2.
Recent events (2)
  • — I (S) $2672.5
  • — Z (S) $5345

View Great Lakes Polymer Technologies, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341836799.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.