ARCHER, FL —
OSHA Inspection: WATSON C&D, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of WATSON C&D, LLC in 12890 NE STATE ROAD 24, ARCHER, FL 32618 (NAICS 562998). OSHA activity number 341846806.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WATSON C&D, LLC
- Site address
- 12890 NE STATE ROAD 24
- City
- ARCHER
- State
- FL
- ZIP
- 32618
- Mailing
- 12890 NE STATE ROAD 24, ARCHER, FL 32618
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562998
- Employees
- 25
- Ownership type
- A
Citations
6 citations on file for this inspection.
5(a)(1)
- Issued
- Nov 22, 2016
- Abate by
- Jan 11, 2017
- Penalty
- Initial $4,988 · Current $4,988
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees a. On or about October 18, 2016 the employer was using Polyvinyl Chloride (PVC) pipe to supply compressed air with a gauged air pressure of 110 pounds per square inch (psi) to operate portable hand tools throughout the welding area. The PVC pipe was not approved for use with compressed air and could fail or rupture, exposing employees to laceration and puncture hazards.
Recent events (2)
- — I (S) $4988
- — Z (S) $4988
1910.253 B05 III C
- Issued
- Nov 22, 2016
- Penalty
- Initial $4,988 · Current $0 Reduced
General-duty citation text
29 CFR 1910.253(b)(5)(iii)(C): The employer did not ensure that the employee was standing to one side on the outlet rather than in front of it when opening the cylinder valve: a. On or about October 17, 2016, an employee opened the valve to a portable acetylene bottle stored in the welding area, was engulfed with flames from a spontaneous ignition of the acetylene and received burn-type injuries to the right hand and forearm.
Recent events (2)
- — I (S) $0
- — Z (S) $4988
1910.253 B05 III J
- Issued
- Nov 22, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(5)(iii)(J): The employer did not ensure that cylinders were always opened slowly: a. On or about October 17, 2016, an employee quickly opened the inlet valve of the compressed gas bottle to test for contents, was engulfed with flames from a spontaneous ignition of the acetylene and received burn-type injuries to the right hand and forearm.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Nov 22, 2016
- Abate by
- Feb 2, 2017
- Penalty
- Initial $4,988 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. On or about October 18, 2016 employees wee exposed to electrical shock hazards because the branch circuits within the breaker box were not properly labeled or identified. The employer fails to assure effective protection against electric shock or other employee injuries as required by the standard, because the circuit breakers inside the breaker box were not properly marked to identify which circuit they control.
Recent events (2)
- — I (S) $0
- — Z (S) $4988
1910.303 B07 I
- Issued
- Nov 22, 2016
- Abate by
- Jan 11, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment. a. On or about October 18, 2016 the employer did not ensure that unused circuit breaker openings in the breaker panel box were effectively closed to prevent electrical shock incidents.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 H03
- Issued
- Nov 22, 2016
- Abate by
- Feb 13, 2017
- Penalty
- Initial $400 · Current $400
General-duty citation text
29 CFR 1910.1200(h)(3): The employee training did not include the requirements of 29 CFR 1910.1200(h)(3)(i) through (h)(3)(iv): a. On or about October 17, 2016 employees were not trained to recognize the hazards of working with hazardous chemicals stored in compressed gas cylinders, such as, but not limited to, acetylene gas and were exposed to burn hazards.
Recent events (2)
- — I (O) $400
- — Z (O) $400
More inspections at Watson C&D, LLC
View Watson C&D, LLC's full OSHA safety record →
More inspections in this industry (NAICS 562998)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341846806.