FORT CARSON, CO —
OSHA Inspection: BERWICK ELECTRIC COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BERWICK ELECTRIC COMPANY in 1650 COCHRANE CIRCLE, FORT CARSON, CO 80913 (NAICS 238210). OSHA activity number 341955433.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BERWICK ELECTRIC COMPANY
- Site address
- 1650 COCHRANE CIRCLE
- City
- FORT CARSON
- State
- CO
- ZIP
- 80913
- Mailing
- 3450 N NEVADA AVE. SUITE 100, COLORADO SPRINGS, CO 80913
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 10
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.950 B02 V
- Issued
- Apr 21, 2017
- Abate by
- May 10, 2017
- Penalty
- Initial $11,408 · Current $12,675
General-duty citation text
29 CFR 1926.950(b)(2)(v): The employer did not ensure each qualified employee was trained and competent in the recognition of electrical hazards to which the employees may be exposed and the skills and techniques necessary to control or avoid these hazard: (a) On or about November 28, 2016, employees were exposed to shock and electrocution hazards due to working on or near energized 12,470 volt HLV/cc switch gear. Employees did not have the skills, such as being knowledgeable of the schematics and the operation of the switch gear, necessary to control or avoid these hazards. Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
- — F (S) $12675
- — C (S) $11408
- — Z (S) $11408
1926.952 A02
- Issued
- Apr 21, 2017
- Abate by
- May 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.952(a)(2): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (b), (c), and (d) of this section with the employees involved before they start each job: (a) On or about November 28, 2016, Berwick Electric Company, the exposing employer, did not conduct an effective job briefing that complied with paragraphs (b), (c), and (d) of this section, for the electrical distribution line terminations at the 12,470 volt HLC/cc switch gear located in the mechanical room. Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1926.961 C02
- Issued
- Apr 21, 2017
- Abate by
- May 10, 2017
- Penalty
- Initial $11,408 · Current $0 Reduced
General-duty citation text
29 CFR 1926.961(c)(2): The employer did not ensure that all switches, dis-connectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be de-energized are open and the employer did not render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work: (a) On or about November 28, 2016, the employer exposed employees to shock and electrocution hazards by not de-energizing and rendering the 12,470 volt HLV/cc switch gear inoperable prior to employees exposure. Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
- — F (S) $0
- — C (S) $11408
- — Z (S) $11408
1926.961 C06
- Issued
- Apr 21, 2017
- Abate by
- May 10, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.961(c)(6): After the applicable requirements in paragraphs (c)(1) through (c)(5) of this section had been followed and the system operator gave a clearance to the employee in charge, the employer did not ensure that the lines and equipment were de-energized by testing the lines and equipment to be worked with a device designed to detect voltage: a) On or about November 28, 2016, the employer did not test the 12,470 volt HLV/cc switch gear to determine that the switch gear was de-energized before employees started to work. Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
More inspections at Berwick Electric Company
View Berwick Electric Company's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341955433.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.