OSHA Inspection: BERWICK ELECTRIC COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of BERWICK ELECTRIC COMPANY in 1650 COCHRANE CIRCLE, FORT CARSON, CO 80913 (NAICS 238210). OSHA activity number 341955433.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Berwick Electric Company — free Get an email when a new federal OSHA severe-injury report for Berwick Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
1650 COCHRANE CIRCLE
City
FORT CARSON
State
CO
ZIP
80913
Mailing
3450 N NEVADA AVE. SUITE 100, COLORADO SPRINGS, CO 80913
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
10
Ownership type
A

4 citations on file for this inspection.

1926.950 B02 V

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 21, 2017
Abate by
May 10, 2017
Penalty
Initial $11,408 · Current $12,675
29 CFR 1926.950(b)(2)(v): The employer did not ensure each qualified employee was trained and competent in the recognition of electrical hazards to which the employees may be exposed and the skills and techniques necessary to control or avoid these hazard:     (a) On or about November 28, 2016, employees were exposed to shock and electrocution hazards due to working on or near energized 12,470 volt HLV/cc switch gear.  Employees did not have the skills, such as being knowledgeable of the schematics and the operation of the switch gear, necessary to control or avoid these hazards.        Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
  • — F (S) $12675
  • — C (S) $11408
  • — Z (S) $11408

1926.952 A02

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 21, 2017
Abate by
May 10, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.952(a)(2): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (b), (c), and (d) of this section with the employees involved before they start each job:  (a) On or about November 28, 2016, Berwick Electric Company, the exposing employer, did not conduct an effective job briefing that complied with paragraphs (b), (c), and (d) of this section, for the electrical distribution line terminations at the 12,470 volt HLC/cc switch gear located in the mechanical room.    Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.961 C02

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 21, 2017
Abate by
May 10, 2017
Penalty
Initial $11,408 · Current $0 Reduced
29 CFR 1926.961(c)(2): The employer did not ensure that all switches, dis-connectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be de-energized are open and the employer did not render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work:    (a) On or about November 28, 2016, the employer exposed employees to shock and electrocution hazards by not de-energizing and rendering the 12,470 volt HLV/cc switch gear inoperable prior to employees exposure.     Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
  • — F (S) $0
  • — C (S) $11408
  • — Z (S) $11408

1926.961 C06

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 21, 2017
Abate by
May 10, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.961(c)(6): After the applicable requirements in paragraphs (c)(1) through (c)(5) of this section had been followed and the system operator gave a clearance to the employee in charge, the employer did not ensure that the lines and equipment were de-energized by testing the lines and equipment to be worked with a device designed to detect voltage:    a) On or about November 28, 2016, the employer did not test the 12,470 volt HLV/cc switch gear to determine that the switch gear was de-energized before employees started to work.    Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View Berwick Electric Company's full OSHA safety record →