Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NEXTERA ENERGY, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of NEXTERA ENERGY, INC. in 9700 LILY GRADE RD TRANSMISSION CORRIDOR ACROSS THE STREET FROM THE PEACE RIVER ELECTRIC CO-OP - PINE LEVEL SUBSTATION, ARCADIA, FL 34265 (NAICS 221119). OSHA activity number 342052172.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nextera Energy, INC. — free Get an email when a new federal OSHA severe-injury report for Nextera Energy, INC. is published. One employer, no account, unsubscribe in one click.
Site address
9700 LILY GRADE RD TRANSMISSION CORRIDOR ACROSS THE STREET FROM THE PEACE RIVER ELECTRIC CO-OP - PINE LEVEL SUBSTATION
City
ARCADIA
State
FL
ZIP
34265
Mailing
P.O. BOX 14000, JUNO BEACH, FL 33408
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221119
Employees
20
Ownership type
A

1 citation on file for this inspection.

1910.333 C03 III

Serious Gravity 10 1 instance 3 exposed
Issued
Apr 25, 2017
Abate by
Jun 12, 2017
Penalty
Initial $12,675 · Current $12,675
29 CFR 1910.333(c)(3)(iii): And vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines shall be operated so that a clearance of 10 ft. (305 cm) is maintained; if the voltage is higher than 50kV, the clearance shall be increased 3 in. (10 cm) for every 10kVover that voltage (as referenced by 1910.180(j)).  a) At the staging area, the qualified person allowed an uninsulated crane boom/load line to make contact with or approach within 4 feet, 6 inches of a power line energized at 138kV, on or about November 29, 2016.
Recent events (1)
  • — Z (S) $12675

View Nextera Energy, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342052172.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.