OSHA Inspection: BUREAU OF LAND MANAGEMENT - ELKO DISTRICT OFFICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT - ELKO DISTRICT OFFICE in 3900 EAST IDAHO STREET, ELKO, NV 89801 (NAICS 924110). OSHA activity number 342055928.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bureau of Land Management - Elko District Office — free Get an email when a new federal OSHA severe-injury report for Bureau of Land Management - Elko District Office is published. One employer, no account, unsubscribe in one click.
Site address
3900 EAST IDAHO STREET
City
ELKO
State
NV
ZIP
89801
Mailing
3900 EAST IDAHO STREET, ELKO, NV 89801
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924110
Employees
90
Ownership type
D

6 citations on file for this inspection.

1910.219 D01

Serious Gravity 5 1 instance 12 exposed
Issued
Apr 20, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):   (a) HVAC Room: Employees were exposed to caught in hazards while working in and around the York Induction Motor, Model Number 023 with an unguarded pulley.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Repeat Gravity 5 1 instance 10 exposed
Issued
Apr 20, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) HVAC Room: Employees are exposed to electric shock/fire hazards by using a relocatable power tap spliced to a re-wired relocatable power tap to energize the Broadband Internet and an Echo Labs monitor.  THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1166294, CITATION 02, ITEM NUMBER 003 AND WAS AFFIRMED AS A FINAL ORDER ON DECEMBEBER 9, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 702 NORTH INDUSTRIAL WAY, ELY, NEVADA 89301.
Recent events (1)
  • — Z (R) $0

1910.303 F02

Repeat Gravity 5 1 instance 15 exposed
Issued
Apr 20, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):   Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  (a) IT Room: The employer failed to mark and identify electrical power panel and branch circuit breakers as required thereby exposing employees to shock/fire hazards.  THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 924903, CITATION 01, ITEM NUMBER 009 AND WAS AFFIRMED AS A FINAL ORDER ON NOVEMBER 8, 2013, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, ELY DISTRICT, HC BOX 33500, 702 NORTH INDUSTRIAL WAY, ELY, NEVADA 89301.
Recent events (1)
  • — Z (R) $0

1910.303 G01

Repeat Gravity 5 1 instance 20 exposed
Issued
Apr 20, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a) IT Room: Employees are exposed to electric shock/fire due to electrical Panel being blocked by cabinet with computer monitor and keyboard.  THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1154521, CITATION 01, ITEM NUMBER 001 AND WAS AFFIRMED AS A FINAL ORDER ON OCTOBER 26, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 3405 WHITE LAKE PARKWAY, RENO, NEVADA 89508.
Recent events (1)
  • — Z (R) $0

1910.305 B02 I

Repeat Gravity 5 3 instances 30 exposed
Issued
Apr 20, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  (a) IT Room (Modular): Employees are exposed to electric shock/fire hazards with electrical outlet missing a faceplate and exposed electrical wiring.  (b) Telecom Room (Modular): Employees are exposed to electric shock/fire hazards with electrical outlet missing a faceplate and exposed electrical wiring.  (c) Natural Resources Trailer: Employees are exposed to electric shock/fire hazards with electrical outlet missing a faceplate and exposed electrical wiring.  THE DEPARTMENT OF THE INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 513138, CITATION 01, ITEM NUMBER 005 AND WAS AFFIRMED AS A FINAL ORDER ON December 11, 2012 WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT - TUSCARORA FIELD OFFICE, 3900 EAST IDAHO STREET, ELKO, NEVADA 89801.
Recent events (1)
  • — Z (R) $0

1910.305 G01 IV C

Repeat Gravity 5 1 instance 15 exposed
Issued
Apr 20, 2017
Abate by
May 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings:   (a) Records Cubicle: Employees are exposed to electric shock/fire hazards by using a relocatable power tap which is run through door.  THE U. S. DEPARTMENT OF INTERIOR, BUREAU OF LAND MANAGEMENT WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1155473, CITATION 01, ITEM NUMBER 002 AND WAS AFFIRMED AS A FINAL ORDER ON OCTOBER 26, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT BUREAU OF LAND MANAGEMENT, 5665 MORGAN HILL ROAD, CARSON CITY, NEVADA 89701.
Recent events (1)
  • — Z (R) $0