Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPARTMENT OF JUSTICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF JUSTICE in 13777 AIR EXPRESSWAY BLVD., VICTORVILLE, CA 92394 (NAICS 922140). OSHA activity number 342082716.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Justice — free Get an email when a new federal OSHA severe-injury report for U.S. Department of Justice is published. One employer, no account, unsubscribe in one click.
Site address
13777 AIR EXPRESSWAY BLVD.
City
VICTORVILLE
State
CA
ZIP
92394
Mailing
USP VICTORVILLE P.O. BOX 5400, ADELANTO, CA 92301
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
800
Ownership type
D

10 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 3 instances 6 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  a) At the Federal Correctional Institute -2, Education Office' rooms EM 140 and 144, the exit access was reduced to 16 and 27 inches, employees had to maneuver around the desk and furniture to get out through the narrowed exit access, employee was subjected to fire hazards.  b) At FCI-2 Commissary area sale station, the exit access was reduced to 14 inches, employees had to maneuver around the counter and the freezer to get out through the narrowed exit access.  c) At FCI-2 Special Housing Unit, E-138 counselor's office, exit access was reduced to 23 inches, employees had to maneuver around the desk and furniture to get out through the narrowed exit access.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.   a) At FCI -2 Tool room, the portable fire extinguisher was obstructed by trash container, it was not available for immediate use by employees.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks.  a) At the Federal Correctional Institute -2, Facilities General Maintenance Shop area, the Wilton drill press did not have a guard exposing employees to rotating parts.
Recent events (1)
  • — Z (S) $0

1910.212 A05

Serious Gravity 5 1 instance 3 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(5): Fan blade guards were not provided where the periphery of the blades was less than seven feet above the floor or working level and had openings larger than one half inch:  a) At the Federal Correctional Institute -2, Facilities general area, the industrial fan used for air circulation energized in the floor area had an opening of about five (5) inches exposing employees to the rotating fan blades.
Recent events (1)
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 2 instances 4 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.  a) At the Federal Correctional Institute 2, Balers B2-02-VIX and S-01 used for compaction were missing knock-outs in their control panels, exposing employees to potential electric hazards or electric shock.
Recent events (1)
  • — Z (S) $0

1910.303 F03

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(3): The markings required were not sufficiently durable to withstand the environment involved:  a) At the Federal Correctional Institute 2, Recycle Storage, the Baler CC3-01 control lights used for compacting recycle materials  were not durably marked and un-readable, employees were exposed to compaction hazards.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.   a) At the Federal Correctional Institute 2 Commissary Utility closet PS 127, the buffer's power cord used for house keeping did not have a ground pin, exposing employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  a) At FCI -2, Facilities general maintenance shop area, the power snake's cord used for un-clogging utilities had damaged insulation, outer sheathing was torn and it is missing its ground prong, exposing employees to electrical shock hazards.
Recent events (1)
  • — Z (S) $0

1910.1200 F05 I

Serious Gravity 1 4 instances 6 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein.  a) At FCI -2 Dental Office, there were un-marked plastic containers, subjecting employees to health hazards.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Repeat Gravity 5 5 instances 8 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  a) At the Federal Corrections Institute -2, EF-149 unit conference room, a re-locatable power tap was used to plug-in a refrigerator, a coffee pot and a microwave oven, overloading re-locatable power tap would subject employees to electrical fire hazards.  b) At FCI-2 Commissary sale station, a re-locatable power tap was used to plug-in a refrigerator.  c) At FCI-2 Education Tech's Office,  re-locatable power taps used for computers and monitors were daisy chained, one re-locatable power tap was connected to the other.  d) At FCI-2 Laundry services area, re-locatable power taps used sewing machines were daisy chained, one re-locatable power tap was connected to the other.  e) At FCI-2 Receiving and Discharge records office, re-locatable power taps used for inmate management systems were daisy chained, one re-locatable power tap was connected to the other.  The Federal Bureau of Prisons was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 524558, citation number 1, item number 1 and was affirmed as a final order on 8/15/2012, with respect to a workplace located at 5701 8th Street, Dublin, CA 94568.
Recent events (1)
  • — Z (R) $0

View U.S. Department of Justice's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342082716.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.