Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPARTMENT OF JUSTICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF JUSTICE in 13777 AIR EXPRESSWAY BLVD., VICTORVILLE, CA 92394 (NAICS 922140). OSHA activity number 342083243.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Justice — free Get an email when a new federal OSHA severe-injury report for U.S. Department of Justice is published. One employer, no account, unsubscribe in one click.
Site address
13777 AIR EXPRESSWAY BLVD.
City
VICTORVILLE
State
CA
ZIP
92394
Mailing
USP VICTORVILLE P.O. BOX 5400, ADELANTO, CA 92301
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
800
Ownership type
D

10 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 4 instances 4 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  a) At the Federal Prison Camp Dormitory Counselor's Office, exit access was reduced to 22 inches, employees had to maneuver around the desk and file cabinet to get out through the narrowed exit access, employees were subjected to fire hazards.  b) At the Recreation Office, exit access was reduced to 23 inches, employees had to maneuver around the desk and furniture to get out through the narrowed exit access.  c) At Staff Psychologist Office, exit access was reduced to 25 inches, employees had to maneuver around the desk and furniture to get out through the narrowed exit access.  d)) At Commissary Warehouse Supervisor's Office, exit access was reduced to 26 inches, employees had to maneuver around the desk and furniture to get out through the narrowed exit access.
Recent events (1)
  • — Z (S) $0

1910.165 E

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.165(e): Manually operated actuation devices for use in conjunction with employee alarms were not unobstructed, conspicuous and readily accessible.  a) At the Federal Prison Camp Recreation area indoor cardio, the two manual pull fire actuation alarms were obstructed by the inflated yellow balls, they were not readily accessible by employees.
Recent events (1)
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.  a) At the Federal Prison Camp Computer Lab, the energized wall outlet used to plug-in computers have a missing knock-out, exposing employees to potential electric hazards or electric shock.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 3 instances 4 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.   a) At the Federal Prison Camp Dormitory Photography room, the power cord cart used for electronic equipment did not have a ground pin, exposing employees to electrical hazards.  b) At the Staff Psychologist's Office, the power cart used to plug-in TV and VCR was missing a ground pin.   c)  At the Food Service Scullery area, the fly diffuser light was missing a ground pin.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  a) At the Federal Prison Camp Admin building, the outdoor outlet used to plug-in the medical cart did not have a cover installed, exposing employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 2 instances 4 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  a) At the Federal Prison Camp Dormitory Counselor's Office, the brown extension cord used for electrical appliances had been plugged-in for more than ninety (90) days, subjecting employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:  a) At the Federal Prison Camp Training Center Assembly room, the flexible cord used for electrical appliances was run through walls under the sink, exposing employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 2 instances 4 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.  a) At the Federal Prison Camp Receiving and Discharge, the Wilson Jones shredder did not have strain relief, flexible cord's insulation was being pulled away from its outer sheathing.  Employees were exposed to electrical shock hazards.  b) At the Camp Garage, the brake lathe machine did not have strain relief, flexible cord's insulation was being pulled away from its outer sheathing.  Employees were exposed to electrical shock hazards.
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 1 2 instances 4 exposed
Issued
Mar 29, 2017
Abate by
Apr 12, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  a) At the Federal Prison Camp Dormitory Leisure room, the LG TV's power cord used for entertainment had its damaged insulation repaired and taped, exposing employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Repeat Gravity 5 5 instances 8 exposed
Issued
Mar 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  a) At the Federal Prison Camp Dormitory Counselor's Office, re-locatable power taps used for computers and a refrigerator were daisy chained, one re-locatable power tap was connected to the other.  Overloading re-locatable power tap would subject employees to electrical fire hazards.  b) At the Chaplain's Office, a re-locatable power tap was used to plug-in computers and a refrigerator.  c) At the Drug and alcohol coordinators office,  re-locatable power taps used for computers and monitors were daisy chained, one re-locatable power tap was connected to the other.  d) At the Education Culinary Arts Office, a re-locatable power tap was used for coffee pot and microwave oven.  e) At the USP Power House, a re-locatable power tap was used for a toaster oven, a refrigerator and a waffle maker.  The Federal Bureau of Prisons was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 524558, citation number 1, item number 1 and was affirmed as a final order on 8/15/2012, with respect to a workplace located at 5701 8th Street, Dublin, CA 94568.
Recent events (1)
  • — Z (R) $0

View U.S. Department of Justice's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342083243.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.