SAN JUAN, PR —
OSHA Inspection: U.S. POSTAL SERVICE-GPO
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. POSTAL SERVICE-GPO in 585 FD ROOSEVELT AVE., SAN JUAN, PR 00936 (NAICS 491110). OSHA activity number 342119021.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. POSTAL SERVICE-GPO
- Site address
- 585 FD ROOSEVELT AVE.
- City
- SAN JUAN
- State
- PR
- ZIP
- 00936
- Mailing
- 585 FD ROOSEVELT AVE., SAN JUAN, PR 00936
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 491110
- Employees
- 132
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.304 B03 I
- Issued
- May 1, 2017
- Abate by
- Jun 7, 2017
- Penalty
- Initial $9,054 · Current $5,885 Reduced
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel. On or about 2/17/17, in the male bathroom area, electrical receptacles were not equipped with ground-fault circuit-interrupter protection. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $5885
- — Z (S) $9054
1910.305 B01 I
- Issued
- May 1, 2017
- Penalty
- Initial $9,054 · Current $5,885 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors entered were not effectively closed: On or about 2/17/17, in the main floor hallway area, an electrical junction box did not have all openings covered or closed. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS NOT REQUIRED FOR THIS VIOLATION.
Recent events (2)
- — I (S) $5885
- — Z (S) $9054
More inspections at U.S. Postal Service-Gpo