HOUSTON, TX —
OSHA Inspection: HOUSTON REFINING, LP
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of HOUSTON REFINING, LP in 12000 LAWNDALE, HOUSTON, TX 77017 (NAICS 324110). OSHA activity number 342126489.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HOUSTON REFINING, LP
- Site address
- 12000 LAWNDALE
- City
- HOUSTON
- State
- TX
- ZIP
- 77017
- Mailing
- 12000 LAWNDALE, HOUSTON, TX 77017
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 830
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.119 J02
- Issued
- Jul 31, 2017
- Abate by
- Sep 5, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not implement written procedures to maintain on-going integrity of process equipment as required. On or about February 12, 2017, and at times prior to, in the Sulfur Recovery Unit at Houston Refining in Houston, TX, the employer did not ensure that the frequency of inspections and testing of process piping was performed in accordance with INP-PRO-201, Inspection, Testing, and Repair of Piping when: a) The employer failed to inspect piping circuit 42-TG-1023-CAD (ISO439-0038-04), at the designated 5 year inspection interval (INP-PRO-201 Section 4.2.4.2.2 Table II) at the following locations: 1. TML 1 2. TML 2 3. TML 3 4. TML 4 5. TML 5 6. TML 6 7. TML 7 8. TML 8 9. TML 9 10. TML 10 11. TML 11 12. TML 12 13. TML 13 14. TML 14 15. TML 15 16. TML 16 17. TML 17 b) After the piping was placed in service, subsequent measurements of 42-TG-1023-CAD (ISO439-0038-04), were not made at appropriate intervals to establish corrosion (INP-PRO-201 Section 4.1.10), at the following locations: 1. TML 1 2. TML 3 3. TML 4 4. TML 5 5. TML 6 6. TML 8 7. TML 9 8. TML 10 9. TML 11 10. TML 12 11. TML 14 12. TML 15 13. TML 16 14. TML 17 c) Corrosion under insulation (CUI) inspection was not performed on piping circuit 42-TG-1023-CAD (ISO439-0038-04) to monitor corrosion (INP-PRO-104), at the following locations: 1. TML 1 2. TML 2 3. TML 3 4. TML 4 5. TML 5 6. TML 6 7. TML 7 8. TML 8 9. TML 9 10. TML 10 11. TML 11 12. TML 12 13. TML 13 14. TML 14 15. TML 15 16. TML 16 17. TML 17
Recent events (2)
- — I (S) $0
- — Z (S) $12675
1910.119 J04 III
- Issued
- Jul 31, 2017
- Abate by
- Sep 5, 2017
- Penalty
- Initial $63,375 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience. On or about February 12, 2017, and at times prior to, in the Sulfur Recovery Unit at Houston Refining in Houston, TX, the employer did not ensure that the frequency of inspections and testing of process piping was performed in accordance with Recognized and Generally Accepted Good Engineering practices such as but not limited to API RP 570 (Piping Inspection Code: In-service Inspection, Rating, Repair, and Alteration of Piping Systems), when: a) The employer failed to inspect piping circuit 42-TG-1023-CAD (ISO439-0038-04), at the designated 5 year inspection interval (API RP 570, Table 2) at the following locations: 1. TML 1 2. TML 2 3. TML 3 4. TML 4 5. TML 5 6. TML 6 7. TML 7 8. TML 8 9. TML 9 10. TML 10 11. TML 11 12. TML 12 13. TML 13 14. TML 14 15. TML 15 16. TML 16 17. TML 17 b) After the piping was placed in service, subsequent measurements of 42-TG-1023-CAD (ISO439-0038-04), were not made at appropriate intervals to establish short and/or long term corrosion (API RP 570 Section 7.1.2), at the following locations: 1. TML 1 2. TML 3 3. TML 4 4. TML 5 5. TML 6 6. TML 8 7. TML 9 8. TML 10 9. TML 11 10. TML 12 11. TML 14 12. TML 15 13. TML 16 14. TML 17 c) Corrosion under insulation (CUI) inspection was not performed on piping circuit 42-TG-1023-CAD (ISO439-0038-04) to monitor corrosion (API RP 570 Section 6.4), at the following locations: 1. TML 1 2. TML 2 3. TML 3 4. TML 4 5. TML 5 6. TML 6 7. TML 7 8. TML 8 9. TML 9 10. TML 10 11. TML 11 12. TML 12 13. TML 13 14. TML 14 15. TML 15 16. TML 16 17. TML 17 Houston Refining, LP was previously cited for a violation for this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.119(j)(4)(iii) which is contained in OSHA Inspection Number 1139040, Citation Number 1 item 1b, issued on September 15, 2016 with respect to a workplace located at 12000 Lawndale, Houston, TX. This file became final order on February 29, 2017.
Recent events (2)
- — I (R) $0
- — Z (R) $63375
1910.119 J05
- Issued
- Jul 31, 2017
- Abate by
- Jun 17, 2019
- Penalty
- Initial $63,375 · Current $12,675 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation. On or about February 12, 2017 and at times prior to, in the Sulfur Recovery Unit at Houston Refining in Houston, TX, the employer operated piping circuit 42-TG-1023-CAD (ISO439-0038-04), with a wall thickness less than required for safe operation. Houston Refining, LP was previously cited for a violation fo the Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910.119(j)(5) which is contained in OSHA Inpsection Number 1139040, Citation Number 1 item 2, issued on September 15, 2016 with respect to a workplace located at 12000 Lawndale, Houston, TX. This file became final order on February 29, 2017.
Recent events (2)
- — I (S) $12675
- — Z (R) $63375
More inspections at Houston Refining, LP
View Houston Refining, LP's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342126489.